Max. Continuous Output Current
Inverter
SE12.5K
SE14.4KUS
SE15K
SE16K
SE17K
SE25K
SE27.6K
SE30K
SE33.3K
SE43.2KUS
SE50K
SE55K
SE66.6K
SE66.6KUS
SE75K
SE82.8K
SE100K
SE100KUS 
Three Phase System Installation Guide MAN-01-00505-1.2
Appendix G: Determining the Circuit Breaker Size
Table 1: Circuit Breaker Criteria
(per Phase)
20A
40A
23A
25.5A
26A
38A
40A
36.5A
40A
120A
76A
80A
80A
80A
120A
120A
120A
120A
Recommended Circuit Breaker
25A
50A
32A
32A
32A
50A
50A
50A
50A
150A
100A
100A
100A
100A
150A
150A
150A
150A