[Reset/Run Time]

[Reset/Run Time]
This value sets the time between restart attempts when
[Reset/Run Tries] is a value other than zero.
Important: [Reset/Run Tries] is a cumulative count. This
counter resets to zero if four (4) minutes elapses since the
last fault.

[S Curve Enable]

[S Curve Enable]
This parameter enables a fixed shape S-Curve.
Figure 5.16 S-Curve
Accel/Decel times are double the active accel/decel time
settings.
Important: The setting for [S-Curve Time] must be 0.
Important: If [Stop Select] is set to "S Curve" then the decel
time will be double the active decel setting when a stop
command is provided.
Parameter # 15
Factory Default 1.0 Sec
Parameter Type Read & Write
Units 0.1 Second
Parameter # 57
Factory Default ''Disabled"
Parameter Type Read & Write
Units Text
a
2X Accel Time 1 or 2 '
Accel Time
'
a
1 or 2
Minimum 0.5 Sec
Maximum 30.0 Sec
Settings ''Enabled"
''Disabled"
a
2X Decel Time 1 or 2
Programming
5-33
Enabled
'
Disabled
Decel Time
'
a
1 or 2