Combination Matrix And Ratings / Electrical Data - Carrier 38C Series Installation, Operation And Maintenance Manual

50hz top discharge condensing units
Table of Contents

Advertisement

Combination Matrix and Ratings
Outdoor Model
Indoor Model
38CKPC18DS70
42TPM018-71
38CKPC24DS70
42TPM024-71
38CKPC30DS70
42TPM030-71
38CKPC36DS70
42TPM036-71
38CKPC36DS90
42TPM036-71
38CKPS42DS90
42TPM042-71
38CKPS48DS90
42TPM048-71
38CKPS60DS90
42TPM060-71
38CKPC18DS10
42TPM018-11
38CKPC24DS10
42TPM024-11
38CKPC30DS10
42TPM030-11
38CKPC36DS10
42TPM036-11
38CKPC36DS40
42TPM036-11
38CKPS42DS40
42TPM042-11
38CKPS48DS40
42TPM048-11
38CKPS60DS40
42TPM060-11
Legend for Combination Matrix and Ratings
CFM — Cubic Feet per Minute
EER — Energy Efficiency Ratio
kWh/Yr — kilowatt-hour/Year
Annual Consumption @ T1 kWh/Year — 2,700 x T1
Annual Consumption @ T3 kWh/Year — 1,000 x T3
Notes: Testing as per ISO 13253 testing standard at T1 and T3 conditions.
Electrical Data
Power Supply
Outdoor Model
(V/Ph/Hz)
38CKPC18DS10
38CKPC24DS10
240/1/50
38CKPC30DS10
38CKPC36DS10
38CKPC18DS70
38CKPC24DS70
230/1/50
38CKPC30DS70
38CKPC36DS70
38CKPC36DS40
38CKPS42DS40
415/3/50
38CKPS48DS40
38CKPS60DS40
38CKPC36DS90
38CKPS42DS90
400/3/50
38CKPS48DS90
38CKPS60DS90
Legend for Electrical Data Table
RLA — Rated Load Amps
LRA — Locked Rotor Amps
FLA — Full Load Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
Capacity (Btu/hr)
Indoor
Voltage
Type
T1
230/1/50
Ducted
18,800
230/1/50
Ducted
25,000
230/1/50
Ducted
33,000
230/1/50
Ducted
37,000
400/3/50
Ducted
37,000
400/3/50
Ducted
42,000
400/3/50
Ducted
47,500
400/3/50
Ducted
60,000
240/1/50
Ducted
18,800
240/1/50
Ducted
25,000
240/1/50
Ducted
33,000
240/1/50
Ducted
37,000
415/3/50
Ducted
37,000
415/3/50
Ducted
42,000
415/3/50
Ducted
47,500
415/3/50
Ducted
60,000
Voltage
Compressor
Min
Max
RLA
207
253
6.2
207
253
8.6
207
253
11.4
207
253
12.8
207
253
6.2
207
253
8.6
207
253
11.4
207
253
12.8
360
440
4.5
360
440
6.8
360
440
7.1
360
440
9.5
360
440
4.5
360
440
6.8
360
440
7.1
360
440
9.5
EER (Btu/hr) / W
Power Input (kW)
T3
T1
T3
16,500
11.8
9.0
1.593
21,500
11.8
8.8
2.119
28,500
12.0
9.0
2.750
32,500
12.2
9.5
3.033
32,500
12.2
9.5
3.033
39,500
12.7
9.6
3.307
43,000
12.2
9.0
3.893
51,000
11.8
8.3
5.085
16,500
11.5
9.0
1.628
21,500
11.8
9.0
2.119
28,500
12.0
9.0
2.750
32,500
12.2
9.5
3.033
32,500
12.2
9.5
3.033
39,500
12.7
9.6
3.307
43,000
12.2
9.0
3.893
51,000
11.8
8.3
5.085
FAN
MCA
MOCP
LRA
FLA
48.0
0.52
8.3
48.0
0.52
11.3
64.0
1.50
15.8
64.0
1.50
17.5
48.0
0.52
8.3
48.0
0.52
11.3
64.0
1.50
15.8
64.0
1.50
17.5
35.0
0.80
6.4
43.0
0.80
9.3
52.0
0.80
9.7
67.1
0.80
12.7
35.0
0.80
6.4
43.0
0.80
9.3
52.0
0.80
9.7
67.1
0.80
12.7
Page 5
kWh/Yr
T1
T3
T1
T3
1.833
4,301
1,833
2.443
5,721
2,443
3.167
7,425
3,167
3.421
8,189
3,421
3.421
8,189
3,421
4.115
8,929
4,115
4.778
10,511
4,778
6.145
13,730
6,145
1.833
4,396
1,833
2.389
5,721
2,389
3.167
7,425
3,167
3.421
8,189
3,421
3.421
8,189
3,421
4.115
8,929
4,115
4.778
10,511
4,778
6.145
13,730
6,145
15
15
25
30
15
15
25
30
15
15
15
20
15
15
15
20
AMPS
T1
T3
7.5
8.5
9.5
10.8
12.0
13.8
13.2
15.2
5.0
5.7
5.5
6.5
6.6
7.8
8.5
10.0
7.5
8.4
9.5
10.8
12.0
13.8
13.2
15.2
5.0
5.7
5.5
6.5
6.6
7.8
8.5
10.0

Hide quick links: