Download Print this page

Honeywell EXCEL 5000 Product Data page 6

Distributed i/o
Hide thumbs Also See for EXCEL 5000:

Advertisement

DISTRIBUTED I/O – PRODUCT DATA
NOTE: When the input is identified as a DI point, the
internal pull-up resistor is disabled (see Fig. 6).
Analog input low impedance
for RTD sensors
10 Vdc
25 kOhm
Vi
200 kOhm
GND
Fig. 6. Analog input impedance
Sensors and Transducers
Passive sensors (NTC 20kΩ)
 Room temperature sensor RF20
 Inlet temperature sensor VF20A
 External temperature sensor AF20
Active sensors (0 to 10 V):
 Duct Humidity Sensor H7011A1000
 Duct Humidity Sensor H7012A1009
NV name
nvoAiValue
SNVT_volt_f
nvoAiTemp
SNVT_temp_p
UCPTSensorConfig
UPCTSendOnDelta
SNVT_count
UCPTWireOffset
SNVT_res
EN0B-0090GE51 R0316
Analog input high impedance
(selectable in CARE)
10 Vdc
Vi
200 kOhm
GND
Table 7. L
M
ON
ARK
type
range
0x000 (0.00 mV) to
0x461C4000 (10 V)
0xEC78 (-50 °C) to
0x3A98 (150 °C)
Invalid = 0x7FFF
0 = not used,
9 = 0...10 V with pull-up resistor
4 = NTC20
5 = PT1000
10 = 0...10 V without pull-up
resistor (default = 8)
0 to 4095 (default = 2)
0 to 6553.5 Ω (default = 0)
Active sensors (0 (4) to 20 mA):
 Immersion temperature sensor VF 100
 Air duct temperature sensor LF 100
Wind sensor:
 Wind sensor WS21.
Further connections:
 Temperature sensor terminal TF26
Table 6. Accuracy of analog input sensors.
range
-58 to -4°F (-50 to -20°C)
-4 to 32°F (-20 to 0°C)
32 to 86°F (0 to 30°C)
86 to 158°F (30 to 70°C)
158 to 212°F (70 to 100°C)
212 to 266°F (100 to 130°C)
266 to 302°F (130 to 150°C)
Object NVs for the XFL521B
The value of the input channel connected to a
0...10 V signal after it has been filtered. Voltage
is transmitted in mV. When configured for a
temperature sensor, the channel transmits the
measured resistance.
The value of the input connected to either an
NTC20k or PT1000 sensor with a resolution of
0.1 °C. If the sensor channel is configured as a
voltage input, the temperature value is invalid
(0x7FFF).
Specifies the type of sensor for a particular input
channel.
Specifies the difference in the raw value
measured by the A/D converter is required
before the value of the sensor is transmitted.
Specifies a resistance value to add to the
resistance measured for a temperature sensor.
6
measurement error
(without sensor tolerance)
Pt1000
NTC (20 kΩ)
1.2 K
5.0 K
0.7 K
1.0 K
0.5 K
0.3 K
0.7 K
0.5 K
1.2 K
1.0 K
1.2 K
3.0 K
1.2 K
5.5 K
description

Advertisement

loading

This manual is also suitable for:

Xfl521bXfl522bXfl523bXfl524b