Distributed i/o
Hide thumbs Also See for EXCEL 5000:

Advertisement

Double-Mapping a Data Point
It is possible to preserve the autobinding by mapping the
data point with a second NV. However, the second NV
must then be bound (using a L
ment tool) to another L
W
ON
preserves autobinding, it does require one controller NV
more than if all binding is performed using a L
network management tool (e.g. LonMaker).
Binding to Other Devices
If you wish to bind the NVs of Distributed I/O modules to
other devices (i.e. other than the host Excel 500 controller),
autobinding cannot be used. Instead, you will have to
employ a L
W
network management tool (e.g.
ON
ORKS
LonMaker) to (manually) bind all of the Distributed I/O
modules' NVs.
Troubleshooting (Controller Autobinding)
Wiring Check
NOTE: In the case of CARE 4.0, the controller cannot be
used to perform autobinding. However, you can
use XILON to perform the wiring test.
In the case of Excel 500 controllers with controller firmware
version 2.04.xx, Distributed I/O modules can be checked
out without even having an application loaded in the
controller. This is possible using a special test mode
previously active only for internal I/O modules. This test
mode, accessible through the "Data Point Wiring Check"
option on the second screen of the start-up sequence,
allows manually setting outputs and reading inputs to verify
the I/O wiring. The procedure is described in detail in the
XI581/582 - User Guide (Product Literature No.: EN2B-
0126GE51).
Fig. 43. Distributed I/O module cover and LEDs
Each Distributed I/O module has a green Power ON LED
(L1) and a red L
W
service LED (L2) at the upper left
ON
ORKS
of the faceplate. The L
W
ON
for diagnosing the state of the Distributed I/O module (see
below).
W
network manage-
ON
ORKS
device. While this method
ORKS
W
ON
ORKS
service LED (L2) is used
ORKS
DISTRIBUTED I/O – PRODUCT DATA
Fig. 44. Distributed I/O module troubleshooting
If you have more than one module connected to one
XSL511, you should check the modules to the left and to
the right of the defect module (status of green power LED
L1 and red L
W
ON
ORKS
"working" in Table 20 if L1 is lit up green and if the
L
W
communication is working.
ON
ORKS
Table 20. Troubleshooting of Distributed I/O modules
modules
modules
on left
on right
working
working
no
no
yes
no
yes
yes
In case of problems, check if the behavior is changed if
you:
1. Push the L
W
ON
ORKS
Distributed I/O module. The L
light as long as you push the L
The hardware is defective if this is not the case.
2. Switch the power ON / OFF.
3. Set the rotary HEX switch to an unused address for a
few seconds and then select the correct address. This
will reset the Distributed I/O module.
Please contact Honeywell if the above actions do not solve
the problem.
Service Pin Message and LED
A service pin message is sent when
powering-up or resetting,
transitioning to the configured/online state, or
turning the DIP switch.
27
example
status LED L2). A module is
possible causes
 Power OFF
 CPU not working
 Incorrect wiring
 Sliding bus connector on XSL511
not closed properly
 Defective hardware  contact
your Honeywell dealer
 Sliding bus connector on the left
side not closed properly
 Defective hardware  contact
your Honeywell dealer
 Wrong L
W
address (HEX
ON
ORKS
switch setting)
 Defective hardware  contact
your Honeywell dealer
service button to reconfigure the
W
service LED will
ON
ORKS
W
service button.
ON
ORKS
EN0B-0090GE51 R0316