Operating Instruction Μc3 - York YCSA 120 T Technical Information

Air-condensed water chillers and heat pumps
Table of Contents

Advertisement

Operating Instructions
µC3 control
This control unit is specially programmed to control air-water
chillers and heat pumps with four capacity stages. These
Digital inputs
ID1 - J1/8
General protection (PG)
ID2 - J1/1
Flow switch (FS)
ID3 - J1/9
Remote ON/OFF (ROO)
ID4 - J1/2
Pump 1 protector (Q5)
ID5 - J1/10
Low pressure switch, circuit 1 (LP1)
ID6 - J4/8
High pressure switch, circuit 1 (HP1)
ID7 - J4/1
Thermal protection, compressor 1 (THPC1)
ID8 - J4/9
Thermal protection, compressor 2 (THPC2)
ID9 - J4/2
Thermal protection, fans circuit 1 (THPF 1-2)
ID10 - J4/10
Low pressure switch, circuit 2 (LP2)
ID11 - J7/6
High pressure switch, circuit 2 (HP2)
ID12 - J7/1
Thermal protection, compressor 3 (THPC3)
ID13 - J7/8
Thermal protection, compressor 4 (THPC4)
ID14 - J7/3
Thermal protection, fans circuit 2 (THPF 3-4)
ID15 - J7/9
Remote COOL/HEAT (RCH)
ID18 - J7/5
Pump 2 protector (Q6)
Digital outputs
N01/C1-2
Compressor 1, circuit 1 (K1)
N02/C1-2
Compressor 2, circuit 1 (K2)
N05/C5
Pump 1
N06/C6-7
Compressor 3, circuit 2 (K3)
N07/C6-7
Compressor 4, circuit 2 (K4)
N08/C8-9
Pump 2
N010/C10
Alarm
N011/C11-12
Antifreeze heater, circuit 1-2
N012/C11-12
Backup heater
N013/C13-14
4-way valve, circuit 1 (V4V1)
N014/C13-14
4-way valve, circuit 2 (V4V2)
Analogical inputs
B3 - J2
Coil pressure, circuit 1
B4 - J3
Coil pressure, circuit 2
B5 - J4/13
Water temperature at exchanger intake
B6 - J4/12
Water temperature at exchanger outlet
Analogical outputs
Y3
Fan speed control, circuit 1 (PWM)
Y4
Fan speed control, circuit 2 (PWM)
32
are distributed in two independent cooling circuits with two
tandems that act upon a common water circuit. Both systems
have two fans each, with speeds controlled by pressure sen-
sors. This control unit operates by means of the following
intakes and outlets.