York YCSA 120 T Technical Information page 39

Air-condensed water chillers and heat pumps
Table of Contents

Advertisement

-H- Unit configuration
DESCRIPTION
Unit type
Number of compressors / circuits
Rotation of compressors
Number of evaporators
Driver number (EVD400)
Cycle inverting valve logic
Number of pumps
Pump operation
Rotation of pumps
Number of hours for pump rotation
Enable ON/OFF digital input
Enable WINTER/SUMMER digital input
Enable ON/OFF with Monitor
Enable WINTER/SUMMER with Monitor
Inversion delay SUMMER/WINTER operation
Monitor protocol
Communication speed sel.
ID number for Monitor
Enable language selection at commissioning
Restore default values (Attention!)
RANGE
0 - 7
LIFO
FIFO
TIME
CUSTOM
1 - 2
0-1-2-4
NO/NC
1 - 2
ON WITH COMP. ON
ALWAYS OFF
ALWAYS ON
SAFETY ON/ OFF
START TIME
0-9999
Y/N
Y/N
Y/N
Y/N
CAREL
MODEM GSM
ANALOGUE MODEM
RS 232
LONWORKS
MODBUS
1200; 2400; 4800;
9600; 19200
0-200
Y/N
Y/N
UNIT
VALUE
2 (CHILLER)
-
3 (HP)
-
4 / 2
-
FIFO
-
1
-
0
-
NC
1 (SINGLE)
-
2 (DUAL PUMP
ACCESSORY)
ALWAYS ON
-
TIME
hours
12
-
NO
-
NO
-
NO
-
NO
sec
10
-
CAREL
bauds
19200
-
1
-
Y
-
N
39