2. Setting by means of the water temperature at the ex-
changer outlet.
Thermostatic control is based on the temperature value
detected by probe B6.
The set point value (STPM) and the regulating band (RBM)
define a neutral temperature zone (NZ).
- The temperature values comprised between the set point
and the set point plus the band (STPM ≤ Temperature
≤ STPM + RBM) do not cause compressor ON/OFF cy-
cles.
- Temperature values above the set point plus the band (Tem-
perature > STPM + RBM) cause compressor operation.
�����
�����
STPM
Set point
RBM
Control band
NZ
Neutral zone
EOWT
Water temperature at exchanger outlet
DonZ
Compressor ON zone
DoffZ
Compressor OFF zone
TVD
Differential of phase input/output time variations
- Temperature values below the set point (Temperature
The compressor ON/OFF process is governed by a variable
delay period.
As of the time differential calculated as a delay, and in accord-
ance with the average temperature for probe B6, the control
system modulates ON/OFF cycles of the compressors.
If value 0 is set, the minimum delay increase/decrease time
of a call for power disables this function.
There is a differential temperature, which is different for opera-
tion in heat or cool cycle (below or above...), that turns off all
devices installed to avoid excessive heating/cooling.
���
���
�����
��
�����
����
< STPM) turn the compressors off.
���
����
����
HTON
Stage activation maximum time delay
LTON
Stage activation minimum time delay
HT OFF Stage deactivation maximum time delay
LT OFF Stage deactivation minimum time delay
t
Time
����
���������
43