Electrical Characteristics - York YCSA 120 T Technical Information

Air-condensed water chillers and heat pumps
Table of Contents

Advertisement

Electrical characteristics

Power sup-
Model
ply V.ph.Hz.
YCSA-H
120
YCSA 120
400.3.50
YCSA-H
150
YCSA 150
Limits of use
Voltage limits
Model
Nominal at 400
Minimum Maximum
YCSA
342
436
YCSA-H
(1) At lower water temperatures, it is advisable to use glycol type antifreeze mixtures. Minimum T° with glycol -5° C (2) IPESL - SdM - UMT - TÜV, 38°
C SAQ, 40° C DUTCH. (3) 45° C if intake air is -below 0° C.
Prior to final approval of the installation
Check:
- That voltage is always between 342 - 436 V.
- That the power supply cable section is at least
equal to the section recommended in the cor-
responding wiring diagrams.
- That operating instructions have been given
to the user.
Compressor
Nominal A
Arranque
Cool
Heat
4 x 18.2
4 x 16.9
118
4 x 17.7
-
4 x 21.4
4 x 21.6
198
4 x 21.4
-
DB air inlet temperature to coil
Operating cycle
Minimum °C
Cool
Heat
-
-18
-10
Nominal kW
A
Cool
Heat
4 x 10.2
4 x 9.25
4 x 9.4
-
4 x 11.8
4 x 12.5
4 x 11.5
-
Maximum °C
Minimum °C
Cool
Heat
Cool
-
46 (2)
6 (1)
20
Fans
Nominal
Nominal
A
W
4 x 2.75
4 x 600
4 x 3.9
4 x 860
Water outlet temperature
Operating cycle
Máximo °C
Heat
Cool
Heat
-
-
15
30
50 (3)
- That the guarantee card has been filled out.
- That maintenance instructions have been
given, or a regular revision contract has been
signed.
Pump
Nominal
Nominal
A
W
5.5
3 180
6.1
3 400
Temp. differential
between the water
outlet and intake
Minimum
Maximum
°C
°C
3
7
31