Level 1 - Programming (User Level)

To gain access to the Level 1 configuration menu
proceed as follows:
1. Press the (▲) and (▼) keys simultaneously and
keep them pressed for a few seconds until the
first programming variable appears on the
display.
2. Release the (▲) and (▼) keys.
3. Select the variable to be modified using the (▲)
and (▼) key.
4. When the variable has been selected it is
possible to:
• display the setting by pressing the SET key
• modify the setting by pressing the SET key
together with the (▲) and (▼) key.

List of Level 1 variables (User Level)

Variables
Explanation
r0
Differential above main SETPOINT*
* SETPOINT see page 9
d0
Defrost interval (hours)
d2
End-of-defrost setpoint.
Defrosting will not take place if the temperature detected by the defrost
sensor is greater than d2 (If the sensor is faulty defrosting is timed)
d3
Max defrost duration (minutes)
d7
Drip duration (minutes)
At the end of defrost, the compressor and fans remain at standstill for time
d7 and the defrost LED on the front panel flashes.
F5
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for time F5 after dripping. This time
begins at the end of dripping. If no dripping has been set, the fan pause
starts directly at the end of defrost.
A1
Minimum temperature alarm
Allows user to define a minimum temperature for the room being
refrigerated. Below value A1 an alarm trips: the alarm LED flashes, the
displayed temperature flashes and the buzzer sounds to indicate the
problem.
A2
Maximum temperature alarm
Allows user to define a maximum temperature for the room being
refrigerated. Above value A2 an alarm trips: the alarm LED flashes, the
displayed temperature flashes and the buzzer sounds to indicate the
problem.
tEu
Evaporator sensor temperature display
10
5. The new settings are saved automatically when
RS8FD402 © Danfoss A/S 2014/11
When configuration values have been set, you
can exit the menu by pressing the (▲) and (▼)
keys simultaneously for a few seconds until the
cold room temperature reappears.
you exit the configuration menu.
OPTYMA
Value
Default
0.2 - 10 K
2K
0 - 24 hours
4 hours
-35 - 45 °C
15°C
1 - 240 min
25 min
0 - 10 min
0 min
0 - 10 min
0 min
-
-45°C
-
+45°C
Displays
read
evaporator
only
temperature
(displays
nothing if
dE =1)