Example no. 1

In this first example we configure the gateway to connect to it one STT with master and
slave lines, two LMS, one standard subsystem and one CMX, in this way:
§ 1 st central station LMS
§ 2 nd central station LMS
§ STT first line
§ STT second line
§ Standard
§ CMX / CF9003
Please note that in this example the two lines are not physically contiguous (they are on
UART 1 and 4) but they are logically contiguous (the network addresses are 0 and 1)
The DIL-Switch settings are as follows:
DIL-Switch
UART 1
S1-4
S1-5
S1-6
UART 2
S2-2
S2-3
S2-4
UART 3
S2-8
S3-1
S3-2
UART 4
S3-6
S3-7
S3-8
UART 5
S4-5
S4-6
S4-7
UART 6
S5-3
S5-4
S5-5
Tab. 13
UART 1
UART 2
UART 3
UART 4
UART 5
UART 6
subsystem
ON
LMS
ON
ON
ON
LMS
ON
ON
ON
STT first line (=CS11)
OFF
OFF
ON
STT second line (=STT)
OFF
ON
OFF
Standard
ON
ON
ON
CMX / CF9003
ON
OFF
network address
0
1
2
3
25
E1481b
06.2000