The control program checks the hardware connections automatically.
In a fault situation a fault message(s) is displayed:
WRONG ENCODER DIR
WRONG GRID DIR
GRID SYNC FAILED
WRONG ROTOR PHASING
Monitor the most important signals as explained below.
For the possible causes and remedies, see ACS800-67(LC) doubly-
fed induction generator control program firmware manual
[3AUA0000071689
(English)].
If everything is in order, the doubly-fed induction generator control
program continues to identify the generator magnetizing reactance.
It is useful to record important signals with the DriveWindow
monitoring PC tool.
01.01 MOTOR SPEED [rpm]
01.10 DC VOLTAGE [V]
01.11 MAINS VOLTAGE [V]
02.01 STATOR IS [RMS]
02.02 STATOR VOLTAGE [V]
02.06 ROTOR IR [RMS]
The figure below shows a typical start in local mode.











,WHP 
 '& 92/7$*( >9@
,WHP 
 52725 ,5 506 >$@
Stop the rotor-side converter with the DriveWindow STOP button.

Stator voltage synchronization test

Monitor the following rotor-side converter signals with DriveWindow
datalogger with 0.3 ms time level. Trigger condition must be 06.07
STATOR U FLUX and trig level 40 with rising edge.
06.03 ROTOR IU
06.04 ROTOR IY
06.07 STATOR U FLUX
06.05 GRID U FLUX
06.08 STATOR Y FLUX
06.06 GRID Y FLUX




,WHP 
 0$,16 92/7$*( >9@
,WHP 
 67$725 ,6 506 >$@
Start-up with medium voltage stator 63




,WHP 
 67$725 92/7$*( >9@
,WHP 
 02725 63((' >USP@
06.03 ROTOR IU
06.04 ROTOR IY
06.07 STATOR U FLUX
06.05 GRID U FLUX
06.08 STATOR Y FLUX
06.06 GRID Y FLUX