In this chapter the drive types and the application explanations for output K
are explained.
Output K can control two drive types, shutters or blinds:
1.
Shutter
The drive moves UP/DOWN, the blind moves UP/DOWN and the louvre
adjustment OPEN/CLOSE.
2.
Blinds
The drive moves the blinds UP and DOWN. In contrast to the shutter
drive type there are no communication objects available for control of
the louvres.
The general functions of the shutter and blinds do not differentiate from one
another. For this reason they are explained in the following based on the
shutter settings.
Total travel time
The total travel time is the time that a shutter requires for a movement from
fully upwards to fully downwards. Should the Room Master receive an UP or
DOWN movement command, the corresponding output is switched and the
shutter is moved in the appropriate direction.
The shutter is moved in this direction until the Room Master receives a
STOP command or the upper or lower limit positions are reached and
the motor is switched off by the end limit switch.