4. Operating modes

The Mod. A 1732 – A 1832 and A 1732B – A 1832B boards can be controlled, either
locally or remotely, through the SY 1527 software interface. For details on SY 1527
system operation, please refer to the User's Manual of this product. The following
sections contain a description of commands available for the board control and status
monitoring.
4.1

Output control and monitoring

For each output channel, it is possible, through the SY 1527 system, to perform the
following operations:
Assign to channel a symbolic name
Set output voltage (VSET)
Set max. output current (ISET)
Set output voltage software limit (SVMAX)
Set voltage ramp-up speed (RAMP-UP)
Set voltage ramp-down speed (RAMP-DOWN)
Set TRIP parameter
Enable/disable POWER ON option
Switch channel ON/OFF
Monitor output voltage (VMON)
Monitor output current (IMON)
Monitor channel status
If the POWER ON option is enabled, the channel, at POWER ON, is restored in the
same condition it was before the POWER OFF or RESET; if this option is disabled, at
POWER ON or after a RESET, the channel is kept OFF independently from its previous
condition.
The following messages may be returned by the SY 1527 when monitoring the channel
status:
OFF
RUP
RDWN
OVC
NPO:
00101/00:17XXx.MUTx/05
THE MOD. A 1732 and A 1832 BOARDS REQUIRE
SY 1527 FIRMWARE VERSION 1.09.04 OR LATER
(channel turned OFF)
(channel ramping up)
(channel ramping down)
(channel in OVERCURRENT condition)