APPLIANCE INFORMATION
2.2

TECHNICAL DATA

DESCRIPTION
Gas flow rate - Max. 10 minutes from lighting
Natural Gas G20
Propane Gas (LPG)
Central Heating
Maximum rated heat input (net)
Minimum heat input
Max. rated heat output 40/30 °C
Max. rated heat output 50/30 °C
Max. rated heat output 80/60 °C
Max. flow temperature
Max. flow temperature to cylinder (with integral optional
diverter valve)
Max. permissible operating pressure
Available pump head at 21 °C system temp. rise
Flue
Flue gas temp. 80/60 °C, rated/min. load
Flue gas temp. 40/30 °C, rated/min. load
CO
level at max. rated heat output (after 30 min)
2
CO
level at min. rated heat output (after 30 min)
2
NOx class
NOx rating
Condensate
Maximum condensate rate
pH value, approx.
Electrical
Electrical power supply voltage
Frequency
Maximum power consumption
Power consumption in standby mode.
General data
Appliance protection rating
Appliance protection rating with mechanical or RF mechanical
timer or FW100 module fitted
Permissible ambient temperatures
Nominal capacity of appliance
Noise output level (Max central heating)
Packaged boiler weight
Total boiler weight
Lift weight
SEDBUK
SEDBUK 2005
Table 4 Technical data i System
6
NATURAL GAS
UNIT
12i
15i
18i
m³/h
1.33
1.63
1.96
kg/h
-
-
-
kW
12.32
15.40
18.48
kW
3.45
4.62
5.54
kW
12.85
16.06
19.28
kW
12.74
15.92
19.11
kW
12
15
18
°C
82
82
82
°C
75
75
75
bar
2.5
2.5
2.5
m
2.0
2.0
2.0
°C
62/56
66/58
70/60
°C
41/33
44/33
48/34
%
9.65
9.8
9.8
%
8.65
9.2
9.2
5
5
4
mg/
39
60
84
kWh
l/h
0.93
1.2
1.5
4.8
4.8
4.8
a.c. V
230
230
230
Hz
50
50
50
W
140
140
140
W
3.5
3.5
3.5
IP
X4D
X4D
X4D
IP
20
20
20
°C
0 - 50
0 - 50
0 - 50
litre
3.9
3.9
3.9
dBA
42
42
42
kg
41
41
41
kg
37.5
37.5
37.5
kg
27.1
27.1
27.1
band
A
A
A
%
90.1
90.1
90.1
LPG
24i
12i
15i
18i
2.67
-
-
-
-
0.96
1.20
1.44
24.62
12.32
15.40
18.48
7.38
5.95
5.95
9.64
25.67
12.85
16.06
19.28
25.45
12.74
15.92
19.11
24
12
15
18
82
82
82
82
75
75
75
75
2.5
2.5
2.5
2.5
2.0
2.0
2.0
2.0
78/63
62/57
66/59
71/61
54/35
43/35
46/36
49/37
9.8
11.0
11.0
11.0
9.2
10.5
10.5
10.5
5
5
5
4
66
44
60
84
2.0
0.7
0.9
1.2
4.8
4.8
4.8
4.8
230
230
230
230
50
50
50
50
140
140
140
140
3.5
3.5
3.5
3.5
X4D
X4D
X4D
X4D
20
20
20
20
0 - 50
0 - 50
0 - 50
0 - 50
3.9
3.9
3.9
3.9
42
42
42
42
41
41
41
41
37.5
37.5
37.5
37.5
27.1
27.1
27.1
27.1
A
A
A
A
90.1
91.4
91.4
91.4
6 720 804 532 (2012/09)
24i
-
1.91
24.62
9.64
25.67
25.45
24
82
75
2.5
2.0
79/64
55/38
11.0
10.5
5
66
1.5
4.8
230
50
140
3.5
X4D
20
0 - 50
3.9
42
41
37.5
27.1
A
92.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenstar 24iGreenstar 12iGreenstar 15iGreenstar 18i