Controller configuration parameters
Display
Description
r01
Cool cycle set point temperature
r02
Cool set point temperature differential
r03
Heat cycle set point temperature
r04
Heat cycle set point temperature differential
Compressor rotation
0= Disabled
r05
1= FIFO type
2= Per operating hours
Type of regulation
0= Proportional. Inlet temperature.
1= Proportional+neutral zone. Inlet temp.
r06
2= Proportional. Outlet temperature
3= Proportional+neutral zone. Outlet temp.
4= By time+dead zone. Outlet temperature (coolers
only)
r07
Neutral zone differential
(If r06=4 only) Maximum activation time. Outlet tem‐
r08
perature.
(If r06=4 only) Minimum activation time. Outlet temper‐
r09
ature.
(If r06=4 only) Maximum deactivation time. Outlet tem‐
r10
perature.
(If r06=4 only) Minimum deactivation time. Outlet tem‐
r11
perature.
r12
(If r06=4 only) Compressor deactivation differential.
r13
Cool cycle minimum set point temperature
r14
Cool cycle maximum set point temperature
r15
Heat cycle minimum set point temperature
r16
Heat cycle maximum set point temperature
A
Temperature
B
First compressor
C
HEAT set point (r03)
HEAT set point (r03) +
D
Differential (r04)
Controller configuration parameters
Level
U
U
U
U
F
F
F
F
F
F
F
F
U
U
U
U
E
COOL set point (r01)
COOL set point (r01) +
F
Differential (r02)
G
Differential /2 (r02 / 2)
H
Second compressor
Operating instructions
VS
Unit
Max.
41 (R/W)
°C
r14
42 (R/W)
°C
50
43 (R/W)
°C
r16
44 (R/W)
°C
50
78 (R/W)
2
79 (R/W)
4
45 (R/W)
°C
50
80 (R/W)
Seconds
999
81 (R/W)
Seconds
999
82 (R/W)
Seconds
999
83 (R/W)
Seconds
999
46 (R/W)
°C
50
47 (R/W)
°C
r14
48 (R/W)
°C
80
49 (R/W)
°C
r16
50 (R/W)
°C
80
A
H
C
B
A
E
User manual
1
1.5
Min.
Value
r13
12
0,3
2
r15
40
0,3
3
0
2
0
0
0
1
r09
120
c04
100
r11
120
c05
100
0
1
-40
6
r13
20
-40
25
r15
45
G
B
A
D
A
H
F
39