User manual
1.5
Operating instructions
Alarm configuration parameters
Parameters
Description
P01
Alarm delay by flow switch at start-up.
P02
Alarm delay by flow switch with unit in operation.
P03
Alarm delay by low-pressure switch at start-up.
Alarm reset
6= High and low-pressure switch manual reset at
P05
third activation in one hour. Antifreeze control is
manually reset
Cool and heat cycle symbols.
1= "Sun" heat cycle, "Snowflake" cool cycle
P06
0= "Sun" cool cycle, "Snowflake" heat cycle
P08
Digital input 1 for phase detector/general alarm
Digital input 2 for flow switch. Do not modify this
P09
parameter
Digital input 6 for remote Cool/Heat selection. Do
P10
not modify this parameter
Low-pressure alarm selection.
0= Inoperative with the compressor OFF
P15
1= Operative with the compressor OFF
P16
High-temperature alarm for return water
P17
High-temperature delay at start-up
High-pressure alarm by transducer
P18
0= Function disabled
P19
Low-temperature alarm for return water
Alarm activation for high and low water temperature
at start-up.
P20
1= function enabled
0= function not enabled
38
Alarm configuration parameters
Level
VS
U
63 (R/W)
Seconds
U
64 (R/W)
Seconds
U
65 (R/W)
Seconds
F
67 (R/W)
F
19 (R/W)
F
69 (R/W)
F
70 (R/W)
F
76 (R/W)
U
38 (R/W)
U
77 (R/W)
Minutes
F
39 (R/W)
U
40 (R/W)
U
20 (R/W)
Unit
Max.
Min.
150
0
120
0
200
0
1
0
1
0
°C
80
-40
250
0
bar
99,9
0,1
°C
80
-40
1
0
Value
20
5
60
6
1
3
1
9
1
30
30
41
10
0