Alarm configuration parameters
Parameters
P01
Alarm delay by flow switch at start-up.
P02
Alarm delay by flow switch with unit in operation.
P03
Alarm delay by low-pressure switch at start-up.
Alarm reset
6= High and low-pressure switch manual reset at
P05
third activation in one hour. Antifreeze control is
manually reset
Cool and heat cycle symbols.
1= "Sun" heat cycle, "Snowflake" cool cycle
P06
0= "Sun" cool cycle, "Snowflake" heat cycle
P08
Digital input 1 for phase detector/general alarm
Digital input 2 for flow switch. Do not modify this
P09
parameter
Low-pressure alarm selection.
0= Inoperative with the compressor OFF
P15
1= Operative with the compressor OFF
P16
High-temperature alarm for return water
P17
High-temperature delay at start-up
High-pressure alarm by transducer
P18
0= function disabled
P19
Low-temperature alarm for return water
Alarm activation for high and low water temper‐
ature at start-up.
P20
1= function enabled
0= function not enabled
Alarm configuration parameters
Description
Level
U
U
U
F
F
F
F
F
U
U
F
U
U
Operating instructions
VS
Unit
Max.
63 (R/W)
Seconds
150
64 (R/W)
Seconds
120
65 (R/W)
Seconds
200
67 (R/W)
19 (R/W)
69 (R/W)
70 (R/W)
76 (R/W)
38 (R/W)
°C
80
77 (R/W)
Minutes
250
39 (R/W)
bar
99,9
40 (R/W)
°C
80
20 (R/W)
User manual
1
1.5
Min.
Value
0
20
0
5
0
60
6
1
0
1
3
1
1
0
1
-40
30
0
30
0,1
41
-40
10
1
0
0
21