York YLCD Series User Manual page 39

Air-condensed water coolers and centrifugal heat pumps
Table of Contents

Advertisement

Unit configuration parameters
Display
Description
Unit model:
2= Water cooler
H01
3= Air-water heat pump
Number of ventilation circuits (do not modify this pa‐
H02
rameter)
No. of evaporating units present (do not modify this
H03
parameter)
No. of compressors per circuit (do not modify this pa‐
H04
rameter)
Pump operation:
0= Absent
1= Always ON
H05
2= ON upon controller call
3= ON upon controller and time call
COOL/HEAT digital input:
0= Absent
H06
1= Present
ON/OFF digital input:
0= Absent
H07
1= Present
H08
Network configuration (do not modify this parameter)
Keyboard locked:
0= Disabled
H09
1= Enabled
Serial direction for monitoring:
H10
0= Future use as terminal
H11
Output configuration (not selectable)
4-way valve logic operation. Activated in heat cycle.
H12
(do not modify this parameter)
Default parameter loading disabled:
0= Disabled
H22
1= Enabled
Modbus protocol setting:
0= Disabled
H23
1= Enabled
Unit configuration parameters
Level
VS
F
54 (R/W)
F
12 (R/W)
F
13 (R/W)
F
55 (R/W)
F
56 (R/W)
U
14 (R/W)
U
15 (R/W)
F
57 (R/W)
U
16 (R/W)
U
58 (R/W)
F
59 (R/W)
F
60 (R/W)
F
18 (R/W)
F
11
User manual
Operating instructions
Unit
Max.
Min.
3
0
1
0
1
0
3
0
1
0
200
1
3
0
3
0
1
0
1
0
1
1.5
Value
3
0
0
2
1
0
0
2
1
1
0
1
1
0
37

Advertisement

Table of Contents
loading

Table of Contents