Connection Of Motors - Remak AeroMaster FP Series Service Instructions Manual

Air handling units
Table of Contents

Advertisement

Other connections
Schemes of electric wiring - electric heaters
El. heater type FPVE ../..
P= 6–31,5 kW
U, V, W, PE, N
- clamps of electric heater power supply. 3f-400V/50Hz
E3, GE
- clamps of safety thermostat
El. heater type FPVE ../..X
P= 12–18 kW
U, V, W, PE, N
- clamps of electric heater power supply. 3f-400V/50Hz
E3,GE
- clamps of safety thermostat
Q31, Q32, Q14
- clamps of electric heater cascade switching 24V DC

Connection of motors

Motors are equipped with protecting thermocontacts
which protect the motor from overheating. Thermocon-
tacts must be connected according to specified conne-
ction.
Single-speed motors are designed for 230V D/400V Y
power supply voltages and connections for electro mo-
tors with output up to 3kW.
Motors are in production wired to wiring box on casing
of fan section. They are standardly intended for voltage
3x 400 V / 50 Hz.
If the delivery contains frequency inverter for control of
motors with output up to 1,5 kW, the electric connection
is then 1x 230 V / 50 Hz.
The same frequency inverter connection applies for
control of two motors up to 0.75 kW (including). The
frequency inverter connection for control of two 1.1 kW
motors is 3x 400V/50 Hz.
If the single-speed motor is additionally connected to an
output controller (frequency inverter), it is necessary to
check, respectively reconnect the motor wiring (correct
connection Y/D in the motor terminal box) in relation to
the power supply voltage (230/400V).
Air handling units
El. heater type FPVE ../..S
P= 6–31,5 kW
U, V, W, PE, N
- clamps of electric heater power supply. 3f-400V/50Hz
E3, GE
- clamps of safety thermostat
Q14, GC
- clamps of electric heater switching 24V DC
El. heater type FPVE ../..X
P= 22,5–31,5 kW
U, V, W, PE, N
- clamps of electric heater power supply. 3f-400V/50Hz
E3,GE
- clamps of safety thermostat
Q31, Q32, Q33, Q14
- clamps of electric heater cascade switching 24V DC
Picture 13 – Drive unit with two motors
Picture 14 – Connection terminal box
9