Variable Heat Power - Immergas INTEC 30 System External Installation Instructions Manual

Wall mounted heating only boiler
Table of Contents

Advertisement

3.15 VARIABLE HEAT POWER.

N.B.: the pressures indicated in the table repre-
sent the differences of pressures at the ends of
the Venturi mixer and can be measured from
the pressure point in the upper part of the sealed
chamber (see pressure test 15 and 16 Fig. 1-11).
INTEC 12 SYSTEM EXTERNAL.
HEAT
GAS
OUTPUT
CONS.
(kW)
(MJ/h)
12,0
49,2
11,0
45,0
10,0
40,8
9,0
36,8
8,0
32,7
7,0
28,7
6,0
24,8
5,0
20,8
4,0
16,8
3,0
12,7
2,3
9,8
INTEC 30 SYSTEM EXTERNAL.
HEAT
GAS
OUTPUT
CONS.
(kW)
(MJ/h)
30,0
121,6
29,0
117,5
28,0
113,4
27,0
109,3
26,0
105,2
25,0
101,1
24,0
97,1
23,0
93,1
22,0
89,0
21,0
85,0
20,0
81,0
19,0
77,0
18,0
73,0
17,0
69,0
16,0
65,0
15,0
61,0
14,0
57,0
13,0
53,0
12,0
49,0
11,0
45,0
10,0
41,0
9,0
36,9
8,0
32,9
7,0
28,8
6,0
24,8
5,7
23,6
The adjustments must be performed using a
digital differential manometer with a scale in
tenths of mm or Pascal. The power data in the
table has been obtained with intake-exhaust pipe
measuring 0.5 m in length. Gas flow rates refer
NG (G20)
BURNER
BURNER
GAS
NOZZLES
FLOW RATE
PRESSURE
(m
/h)
(kPa)
3
1,30
0,52
1,19
0,44
1,08
0,37
0,97
0,30
0,87
0,24
0,76
0,19
0,66
0,15
0,55
0,11
0,44
0,07
0,34
0,05
0,26
0,03
NG (G20)
BURNER
BURNER
GAS
NOZZLES
FLOW RATE
PRESSURE
(m
/h)
(kPa)
3
3,22
0,41
3,11
0,39
3,00
0,36
2,89
0,34
2,79
0,32
2,68
0,30
2,57
0,28
2,46
0,26
2,36
0,24
2,25
0,22
2,15
0,20
2,04
0,19
1,93
0,17
1,83
0,16
1,72
0,14
1,62
0,13
1,51
0,11
1,40
0,10
1,30
0,09
1,19
0,08
1,09
0,06
0,98
0,05
0,87
0,04
0,76
0,03
0,66
0,03
0,62
0,02
to heating values below a temperature of 15°C
and at a pressure of 1013 mbar. Burner pressure
values refer to use of gas at 15°C.
Universal LPG (G31)
BURNER
BURNER
GAS
NOZZLES
FLOW RATE
PRESSURE
(kg/h)
(kPa)
0,96
0,57
0,87
0,48
0,79
0,41
0,71
0,34
0,64
0,28
0,56
0,22
0,48
0,17
0,40
0,12
0,33
0,08
0,25
0,05
0,19
0,03
Universal LPG (G31)
BURNER
BURNER
GAS
NOZZLES
FLOW RATE
PRESSURE
(kg/h)
(kPa)
2,36
0,49
2,28
0,46
2,20
0,43
2,12
0,40
2,05
0,37
1,97
0,35
1,89
0,32
1,81
0,30
1,73
0,28
1,65
0,25
1,58
0,23
1,50
0,21
1,42
0,19
1,34
0,17
1,26
0,16
1,19
0,14
1,11
0,12
1,03
0,11
0,95
0,09
0,87
0,08
0,80
0,07
0,72
0,06
0,64
0,05
0,56
0,04
0,48
0,03
0,46
0,03
22

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the INTEC 30 System External and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Intec 12 system externalIntec 30 combi external