Data Format - Man L23/30DF Project Manual

Power plant, four-stroke genset
Table of Contents

Advertisement

3.3 Data Format

6
Example for Modbus ASCII Data Format:
Extract from Modbus ASCII list
MW 113
71 0
F
Signal fault ZS82 : Emergency stop
(pushbutton)
1
F
Signal fault ZS75 : Turning gear
disengaged
2
F
Signal fault SS84 : Remote stop
3
F
Signal fault SS83 : Remote start
4
F
Signal fault LAH28 : Lube oil level
high
5
F
Signal fault LAL28 : Lube oil level
low
6
F
Signal fault LAH42 : Fuel oil leakage
high
7
F
Signal fault ZS97 : Remote switch
8
F
Signal fault LAH92 : OMD alarm
9
F
Signal fault TAH 29-27 : CCMON
alarm
10
F
Signal fault : Remote reset
11
F
Signal fault LAH98 : Alternator
cooling water leakage alarm
12
F
Signal fault : Emergency generator
mode
13
F
Signal fault : Speed raise
14
F
Signal fault : Speed lower
15
F
Signal fault : Switch isochronous /
droop mode
For this example we assume that the following alarms have been triggered:
Signal fault SS83 : Remote start,
Signal fault LAL28 : Lube oil level low,
Signal fault ZS97 : Remote switch,
Signal fault LAH92 : OMD alarm,
Signal fault TAH 29-27 : CCMON alarm,
Signal fault : Emergency generator mode,
Signal fault : Switch isochronous / droop mode
The Bit-sample of MW 113:
Bit
0
1
2
3
4
Value
0
0
0
1
0
In Modbus ASCII these 16 Bits are grouped in 4 groups each containing 4
Bits and then translated from binary format to hexadecimal format (0-9, A-F)
Binary
Bit 0-3
0001
Bit 4-7
0101
Bit 8-11
1100
1001
Bit 12-15
MAN Diesel & Turbo
5
6
7
8
9
10
11
1
0
1
1
1
0
0
Hex
1
5
C
9
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
SF=1
CMS
binary
12
13
14
15
1
0
0
1