Interfaces To External Systems; Overview - Man L23/30DF Project Manual

Power plant, four-stroke genset
Table of Contents

Advertisement

System description
SaCoS
GENSET
one

3 Interfaces to external systems

3.1 Overview

A detailed signal description is available on the GS Product page in the document
"SaCoSone.GenSet.Interface_description_Vx.x.docx". (Available as PDF)
Control Unit
Control Module
Display Module
EF12LW
Ethernet
USB 2.0A
Created:
03.08.2009
Last change:
16.08.2010
Released:
Temp. alternator
front bearing*
Temp. alternator
rear bearing*
Temp. winding
L1-L3
Alternator CW
leakage alarm*
Actuator (Governor)
R422/RS485
Stop from engine
Remote stop
Remote start
Remote reset of alarms*
Selector switch
local/remote
Remote – lower speed
Remote – raise speed
Common alarm
Ready to start
Engine is running
Start prelub. oil pump
Start cylinder lubrication**
Start preheater control
Start failure
Engine speed
TC Speed
Emergency
generator mode*
Alternator load*
Speed setpoint
Remote shutdown*
Common shutdown
Engine is running
CCM prealarm
This document is property of MAN Diesel & Turbo SE and is entrusted
Karger
to whom it has been handed over. Copying and communicating to third
Karger
parties is only permitted with written consent of MAN Diesel & Turbo!
Connection
Box
Temp. alternator
front bearing*
Temp. alternator
rear bearing*
Temp. winding
L1-L3
Alternator CW
leakage alarm*
Actuator (Governor)
R422/RS485
Stop from engine
Remote stop
Remote start
Remote reset
of alarms*
Selector switch
local/remote
Remote – lower speed
Remote – raise speed
Common alarm
Ready to start
Engine is running
Start prelub.
oil pump
Start cylinder
lubrication**
Start preheater
control
Start failure
Engine speed
TC Speed
Emergency
generator mode*
Alternator load*
Speed setpoint
Remote shutdown*
Common shutdown
Engine is running
CCM Prealarm
CCM Autoshutdown
CCM system failure
Legend:
––– DI/DO = Digital Input/Digital Output
––– AI/AO = Analogue Input/Analogue Output
––– RS422/RS485 = Modbus RTU
––– CAN
= CAN connection
* = option
** = only 32/40
external systems
GS
Alternator
Governor
Ship alarm system/
Ext. Control
Crankcase
Monitoring *
GenSet
Page 11 of 13