Hub And Lug Data - Siemens TYPE VBII Series Application Manual

Safety switches
Table of Contents

Advertisement

General and Heavy Duty

Hub and Lug Data

ECHV300
SSH150
Interchangeable Hubs
Conduit hubs are available for
Type 3R, 12 and 4/4X applications.
30-200A Type 3R Switches are
provided with a conduit hub provision
and a removable hub plate on their top
rainsheds.
Hubs
Conduit
Size
Catalog
(inches)
Number
Type 3R
3/4
ECHA075
1
ECHA100
30A GD Only
1 1/4
ECHA125
3/4
ECHS075
1
ECHS100
1 1/4
ECHS125
60-200A GD
1 1/2
ECHS150
30-200A HD
2
ECHS200
2 1/2
ECHS250
2 1/2
ECHV250
3
ECHV300
400-1200A
3 1/2
ECHV350
4
ECHV400
Type 4 / 4X
3/4
SSH075
1
SSH100
1 1/4
SSH125
1 1/2
SSH150
30-200A
2
SSH200
NOTE: 30-200A. Type 3R Switches have
removable hub plates on rainsheds. 400A and
larger Type 3R Switches have no provisions
for mounting hubs. Drill or punch hole in the
field to accommodate hub size desired.
➀ Hubs suitable for 3R Switches.
➁ Neutral Barrier kits are required on 30-100A switch only and only with 1-Phase, 3W or 3-Phase and 4W loads.
Compression lugs mounting kits are required on 400-1200A switches only.
➂ Provides mounting for a single line or load lug.
➃ Provides mounting for two compression lugs per phase on line or load one per pole required.
➄ Line lugs have wire-bending space and are UL approved for #14-6 conductors.
➅ Max. wire size for height reduced switches is 500 Kcmil (Cu/Al).
➆ All but 60A GD & Compact HD NF switches are also UL approved for #2 Cu/Al conductors.
➇ All 200A Heavy Duty Switches have a wire range & wire bending space for one # 6-300 Kcmil (Cu/Al).
Compression Lug
Neutral Barrier Kit
All Heavy Duty Switches are field con-
vertible for crimp type lugs. When
compression lugs are required for 30-
100A switches, a neutral barrier kit is
required for 1-Phase, 3W or 3-Phase,
4W applications. When compression
lugs are required on 400-1200A
switches, lug mounting kits are
required.
Compression Lug Mounting
and Neutral Barrier Kits
Switch
Ampere
Catalog
Rating
Number
30
HCL612
60 & 100
HCL623
400 ➂
HCL65
Used On
400
HCL65678
& 600 ➃
800
& 1200 ➃
Lugs
30-100A Switches are suitable
for use with 60ºC or 75ºC wire.
100-1200A are suitable for use
with 75ºC rated wire.
Wire Ranges (Line, Load and Standard Neutral)
Switch
Ampere
Rating
#14-8 AWG (Cu/Al) ➄
30GD
30HD
#12-6 AWG (Al) or #14-6 AWG (Cu/Al)
30A HD
#14-2 AWG(Cu/AI)
oversized
60 ➆
#12-2 AWG (Al) or #14-3 AWG (Cu/Al)
60A HD
#14-1/0 AWG (Cu/Al)
oversized
100
#14-1/0 AWG (Cu/Al)
200 ➇
#6 AWG-250 Kcmil (Cu/Al)
400 ➅
1/0 AWG-750 Kcmil (Cu/Al) or
(2) 1/0 AWG-250 Kcmil (Cu/Al)
600 ➅
(2) 1/0 AWG-750 Kcmil (Cu/Al) or
(4) 1/0-250 Kcmil (Cu/Al)
800
(3) 1/0-750 kcmil (Cu/Al) Line and Load or
(6) 1/0-250 kcmil (Cu/Al)
(4) 1/0-250 kcmil (Cu/Al) neutral
1200
(4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
(4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
ECHS200
Kit Description
Neutral Barrier Kit
Neutral Barrier Kit
1 Pole, Compression
Lug Mounting Kit
1 Pole, Compression
Lug Mounting Kit
Factory Installed Only
Wire Range with
Wire-Bending Space
Per NEC Table 373-6
SL0420
Multiple Padlock Accessory
A tamperproof device to provide for
multiple padlocking to meet OSHA or
plant requirements. Accepts up to six
padlocks. Catalog number SL0420.
Standard Carton-12.
Kirk-Key Interlocks
Kirk-Key Interlocks are factory installed
only on Type VII Heavy Duty and Double
Throw Safety Switches.
Interlocks are used to prevent the
authorized operator from making an
unauthorized operation. The interlock
system is a simple method of applying
key interlocks to safety switches so as to
require operation in a predetermined
sequence.
Before consulting the factory, the
following information is required:
• User name and address
• Key number from lock assemblies
on any existing locks to be inter-
locked with
• Complete locking scheme
Consult factory for delivery.
Lug Range
#14-8 AWG (Cu/Al) ➅
#14-2 AWG (Cu/Al)
#14-2 AWG (Cu/AI)
#14-2 AWG (Cu/Al)
#14-1/0 AWG (Cu/Al)
#14-1/0 AWG (Cu/Al)
#6 AWG-300 Kcmil (Cu/Al)
(1) 1/0 AWG-750 Kcmil (Cu/Al) or
(2) 1/0 AWG-250 Kcmil (Cu/Al)
(2) 1/0 AWG-750 Kcmil (Cu/Al) or
(4) 1/0 AWG-250 Kcmil (Cu/Al)
(3) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
(4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
(4) 1/0 AWG-750 Kcmil (Cu/Al) Line and Load
(4) 1/0 AWG-600 Kcmil (Cu/Al) neutral
25