Power supply, diagnostics interface
Hide thumbs Also See for SITOP PSU6200:

Advertisement

Status information
For devices from product group PSU6200, when transferring data via DIS, information about
the actual status of the sending device is transferred in all telegrams in bits 7 - 13.
Bit no. Meaning
1 - 3
Device identifi-
cation
4
Reserved
5 - 6
Telegram iden-
tification
7
DC Okay
8
Service life
9 - 10
Output current
11
Overtempera-
ture shutdown
12
DC OK thresh-
old
13
Parallel mode
SITOP PSU6200 Diagnostics Interface
Application Manual, 04.2019, A5E46632255-1-76
Resolution
Value range
0 - 7
011: PSU6200
-
0 - 3
00: -
01: -
10: -
11: -
0 / 1
0: Output voltage too low
1: Output voltage okay
0 / 1
0: Device age < 90 % nominal
value
1: Device age > 90 % nominal
value
0 - 3
00: Current < 30 % of I
01: Current 30 - 60 % of I
10: Current 60 - 90 % of I
11: Current > 90 % of I
0 / 1
0: Device in operation
1: Device shutdown with latching
due to overtemperature
0 / 1
0: OK threshold low
1: OK threshold high
0 / 1
0: Single mode
1: Parallel mode
2.2 Telegrams for the diagnostics interface (DIS)
Comment
This bit is always "0"
See the following chapter
This bit is an image of the OK LED at the
front of the device
These bits correspond to the LED utilization
rated
display,
rated
maximum current of the last 3 seconds
rated
rated
Device status: in operation or shutdown due
to actual overtemperature or previous over-
temperature condition
This bit specifies the position of the DIP 2 at
the front of the device
This bit specifies the position of the DIP 1 at
the front of the device
Technical description
11