MCAC-UTSM-2008-11
8.3 Quantity of Water in Installation
Model
Minimum water volume (L)
If the total water volume in the system is less than the value in the table above, the additional water tank is
necessary in order to avoid the compressor On/Off frequency.
The minimum size of the water tank is calculated as:
Size of additional water tank(L)=Minimum water volume (L) –Actual water volume(L)

9. Hydraulic Performance

9.1 Pump head curves(*)
Note:
(*) To obtain the useful head of the installation, subtract the pressure drop of the plate heat exchanger.
9.2 Heat exchanger pressure drop (water side)
Model
Water flow
10kW
Pressure drop
Model
Water flow
12 kW
14 kW
Pressure drop
16 kW
Outdoor Unit
MGA-D10/N1
43
3
m
/ h
0.8
1.0
l/sec
0.222
0.278
kPa
26
29
3
m
/ h
1.2
1.4
l/sec
0.333
0.389
kPa
35
39
kPa
28
31
kPa
26
29
MGA-D12/N1
MGA-D14/SN1
50
1.2
1.4
1.6
0.333
0.389
0.444
33
37
42
1.6
1.8
2.0
0.444
0.500
0.556
44
47
50
36
40
43
32
37
41
Hydraulic Performance
MGA-D16/SN1
60
68
1.8
2.0
0.500
0.556
46
50
2.2
2.4
0.611
0.667
53
58
46
50
45
49
2.6
0.722
54
52
21