Troubleshooting
E0: Water flow test malfunction
LED indicates E0
Judge 1: The water pump gets faulty.
Judge 2: Water flow switch gets faulty.
Judge 3: Check whether the water system is blocked.
The ︳T
inlet water
Judge 4: There is air left in the water system.
Judge 5: Check whether the circulation water is
32
No
No
– T
︳>10℃
outlet water
No
No
insufficient
Yes
Check the water pump, and repair or replace it
Yes
Check the water flow switch, and repair or
replace it if necessary.
Yes
Check the water system and clean the filter.
Yes
Yes
Check the water system and make
MCAC-UTSM-2008-11
if necessary.
Exhaust the air.
adjustment.