Capacity Tables
Model
(°C)
Ta. U.R.87%
-5
0
7
10
15
Remark:
Ta: outside air temperature (°C )
Tw : evaporator water outlet temperature (°C)
Pt: heating capacity (kW)
Pa: compressor power input (kW)
Pat: total power input (kW)
Qc: condenser water flow (m
ΔPc: evaporator pressure drop (kPa)
— : conditions outside of operating limits
18
(°C)
35
Tw
Pt (kW)
10.4
Pa (kW)
4.0
Pat (kW)
4.8
3
Qc (m
/h)
1.9
△
Pc (kPa)
25.8
Pt (kW)
13.1
Pa (kW)
4.0
Pat (kW)
4.8
3
Qc (m
/h)
2.3
△
Pc (kPa)
21.1
Pt (kW)
16.2
Pa (kW)
4.1
Pat (kW)
4.9
3
Qc (m
/h)
2.8
△
Pc (kPa)
31.2
Pt (kW)
17.6
Pa (kW)
4.2
Pat (kW)
5.0
3
Qc (m
/h)
3.1
△
Pc (kPa)
36.4
Pt (kW)
19.8
Pa (kW)
4.3
Pat (kW)
5.1
3
Qc (m
/h)
3.5
△
Pc (kPa)
45.4
3
/h)
MGA-D14/SN1
40
45
10.5
10.6
4.4
4.9
5.2
5.7
1.9
1.9
27.2
27.0
13.0
13.0
4.4
4.9
5.2
5.7
2.3
2.3
21.1
21.0
16.1
16.0
4.5
5.0
5.3
5.8
2.8
2.8
31.1
31.0
17.5
17.4
4.6
5.1
5.4
5.9
3.1
3.1
36.2
36.0
19.7
19.6
4.7
5.2
5.5
6.0
3.5
3.5
45.2
45.0
MCAC-UTSM-2008-11
50
—
—
—
—
—
12.9
5.4
6.1
2.3
21.0
15.9
5.5
6.3
2.8
31.0
17.4
5.6
6.4
3.1
35.9
19.4
5.7
6.5
3.5
44.9
Outdoor Unit