Appendix 2. Buffer Memory Allocation - Mitsubishi Electric MELSEC-A Series User Manual

Temperature control module, temperature control module with heater disconnection detection function (hardware)
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

Appendix 2.
Address (Hex.)
CH1 CH2 CH3 CH4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10 Manipulation value (MV)
11
12
13
14 Increased temperature determination flag
15
16
17
18 Transistor output flag
19
1A
1B
1C Heater current process value
1D
1E
1F
20
40
60
80 Input range
21
41
61
81 Stop mode setting
22
42
62
82 Set value (SV) setting
23
43
63
83 Proportional section (P) setting
24
44
64
84 Integral time (D) setting
25
45
65
85 Derivative time (D) setting
26
46
66
86 Alert alarm 1 set value
27
47
67
87 Alert alarm 2 set value
28
48
68
88 Alert alarm 3 set value
29
49
69
89 Alert alarm 4 set value
2A
4A
6A
8A Upper output limiter
2B
4B
6B
8B Lower output limiter
2C
4C
6C
8C Output variation limiter
2D
4D
6D
8D Sensor compensation value setting
2E
4E
6E
8E Adjustment sensitivity (blind section) setting
2F
4F
6F
8F Control output cycle setting
30
50
70
90 First-order delay digital filter setting
31
51
71
91 Control response parameter
Buffer Memory Allocation
Buffer memory address name
Write data error code
Decimal point position
Alert details
Temperature process value (PV)
Unusable
Switch to manual mode completion flag
Unusable
A-2
Setting/selection range
0 to 2
Depends on the input range
0 to 1000(0.0 to 100.0%)
1 to 3600s
0 to 3600s
Depends on the input range
-50 to 1050(-5.0 to 105.0%)
1 to 1000(0.1 to 100.0%/s)
-500 to 500(-5.00 to 5.00%)
1 to 100(0.1 to 10.0%)
1 to 100s
0 to 100s
0 : Slow, 1 : Normal,
2 : Fast