4. Handling

4.1

Precaution when handling

(1) The module case is made of plastic. Be sure not to drop it or subject it
to strong vibration.
(2) Do not remove the module printed circuit boards from the case. It may
cause trouble.
(3) When connecting the wiring, do not allow wire cuttings or other foreign
matter to enter from the top of the module. Remove any foreign matter
from the module.
(4) Tighten the module mounting screws within the following tightening torque
range.
Module mounting screws (M4 screws)
Terminal block terminal screws (M3.5 screws)
Terminal block mounting screws (M4 screws)
Screw
9
Tightening Torque range
78 to 118N
cm (8 to 12kg
[6.93 to 10.40lb
inch]
59 to 88N
cm (6 to 9kg
[5.20 to 7.80lb
inch]
78 to 118N
cm (8 to 12kg
[6.93 to 10.40lb
inch]
cm)
cm)
cm)