Mitsubishi Electric MELSEC-A Series User Manual page 27

Temperature control module, temperature control module with heater disconnection detection function (hardware)
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

Address (Hex.)
CH1 CH2 CH3 CH4
32
52
72
92 AUTO/MAN mode switch
33
53
73
93 Manual output setting
34
54
74
94 Setting change rate limiter
35
55
75
95 AT bias
36
56
76
96 Forward/reverse action setting
37
57
77
97 Upper setting limiter
38
58
78
98 Lower setting limiter
39
59
79
99 CT selection
3A
5A
7A
9A Heater disconnection alert setting
3B
5B
7B
9B Loop disconnection detection determination time
3C
5C
7C
9C Loop disconnection detection dead band
3D
5D
7D
9D Unused channel setting
3E
5E
7E
9E
3F
5F
7F
9F
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC AD AE Standard heater current value
AF
B0
Buffer memory address name
Unusable
Alert alarm 1 mode setting
Alert alarm 2 mode setting
Alert alarm 3 mode setting
Alert alarm 4 mode setting
Alert blind section setting
Number of alert delays
Number of delays for heater disconnection/
current error detection when output is turned off
Temperature increase complete determination
Temperature increase complete soak time set-
ting
PID continue flag
Heater voltage compensation function setting
Transistor output monitor or delay time setting
CT monitor method switch
A-4
Setting/selection range
0 : Auto(AUTO),
1 : Manual(MAN)
-50 to 1050
(-5.0% to 105.0%)
0 to 1000(0.0 to
100.0%min)
±Input range width
0 : Forward action,
1 : Reverse action
Within measurement range
0 : 0.0 to 100.0A,
1 : 0.00 to 20.00A
0 to 100%
0 to 7200s
Input range width
0 : Used, 1 : Unused
0 to 14
0 to 100(0.0 to 10.0%)
0 to 255
3 to 255
1 to 10°C(°F)
0 to 3600min
0 : Stop, 1 : Continue
0 : OFF, 1 : ON
Heater current range
0 to 50(0 to 500ms)
0 : on current/off current,
1 : on current