12.2 Outdoor Unit

12.2.1
Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the [piping length for additional gas], additional refrigerant should be added as shown in
the table.
Table A
Piping size
Horse
Model
Power
(HP)
Gas
Liquid
9.52
Z25****
1.0HP
mm
6.35
Z35****
1.5HP
"
(3/8
)
mm
12.7
Z50****
2.0HP
(1/4
mm
Z60****
2.25HP
"
(1/2
)
Example: For Z25****
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m × 10 g/m =
25 g.
A
= (M / (2.5 × (LFL)
min
A
= Required minimum room area, in m
min
M
= Refrigerant charge amount in appliance, in kg
LFL = Lower flammable limit (0.306 kg/m
h
= Installation height of the appliance: (2.2m for mini cassette & ducted is standard reference installed height)
0
Min.
Std.
Max
Piping
Length
Elevation
A
B
Length
(m)
(m)
(m)
15
3
15
3
5
"
20
3
)
20
3
(5/4)
2
× h
))
0
2
3
)
(2.5m for mini cassette & ducted is minimum installed height given by
manufacturer)
(0.6m for floor console)
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult authorized
dealer/specialist.
This illustration is for
explanation purposes only.
Max.
Piping
Additional
Piping
Length for
Refrigerant
Length
add. gas
(g/m)
(m)
(m)
20
10
7.5
20
10
7.5
30
15
7.5
30
15
7.5
49
Indoor
Indoor
2
A
(m
)
A
min
min
2.2m for
2.5m for
2.2m for
mini
mini
ducted
cassette
cassette
0.64
0.50
0.64
0.71
0.55
0.71
1.37
1.06
1.37
1.37
1.06
1.37
Power supply
cable ( )
Connection
cable ( )
1/4" Liquid
side piping ( )
Gas side
piping ( )
Additional
drain hose ( )
Installation parts you
should purchase ( )
Indoor
2
2
(m
)
A
(m
)
min
2.5m for
0.6m for
ducted
floor console
0.50
8.67
0.55
9.55
1.06
18.48
1.06
N/A