Please file and use this manual together with the service manual for Model No. CU-2E12SBE, CU-2E15SBE, CU-2E18SBE,
CU-3E23SBE,
CU-3E18PBE,
CU-3Z52TBE, CU-3Z68TBE, CU-4Z68TBE, CU-4Z80TBE, CU-5Z90TBE, Order No. PAPAMY1601015CE, PAPAMY1301048CE,
PAPAMY1303046CE, PAPAMY1702035CE, PAPAMY1703049CE, PAPAMY1710082CE.
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
There are special components used in this equipment which are important for safety. These parts are marked by
Diagrams, Circuit Board Diagrams, Exploded Views and Replacement Parts List. It is essential that these critical parts should be replaced
with manufacturer's specified parts to prevent shock, fire or other hazards. Do not modify the original design without permission of
manufacturer.
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
R32 REFRIGERANT
– This Air Conditioner contains and operates with refrigerant R32.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL.
Refer to Commonwealth, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the
installation, maintenance and/or service of this product.
Panasonic
CU-4E23PBE,
CU-4E27PBE,
WARNING
IMPORTANT SAFETY NOTICE
PRECAUTION OF LOW TEMPERATURE
Indoor Unit
CS-Z25UD3EAW
CS-Z35UD3EAW
CS-Z50UD3EAW
CS-Z60UD3EAW
CU-5E34PBE,
CU-2Z35TBE,
CAUTION
Order No: PAPAMY1801010CE
Outdoor Unit
CU-Z25UBEA
CU-Z35UBEA
CU-Z50UBEA
CU-Z60UBEA
Destination
Europe
Turkey
CU-2Z41TBE,
CU-2Z50TBE,
in the Schematic
© Panasonic Corporation 2018.

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-Z25UD3EAW

  • Page 1 – This Air Conditioner contains and operates with refrigerant R32. THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL. Refer to Commonwealth, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation, maintenance and/or service of this product. © Panasonic Corporation 2018.
  • Page 2: Table Of Contents

    Automatic Operation ........82     Refrigeration Cycle Diagram ......25     15.5 Indoor Fan Motor Operation .......82     CS-Z25UD3EAW CU-Z25UBEA   15.6 Powerful Mode Operation ......82     CS-Z35UD3EAW CU-Z35UBEA ....25   15.7 Auto Restart Control ........82  ...
  • Page 3: Safety Precautions

    1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
  • Page 4 WARNING Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant connection inside a building or dwelling or room must be made by brazing or welding. Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a building or dwelling or room.
  • Page 5 CAUTION Do not touch the sharp aluminium fin, sharp parts may cause injury. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture. Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
  • Page 6: Precaution For Using R32 Refrigerant

    2. Precaution for Using R32 Refrigerant  The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
  • Page 7 CAUTION 2-5. No ignition sources  No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
  • Page 8 CAUTION Leak detection methods  Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)  Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
  • Page 9 CAUTION Labelling  Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.  The label shall be dated and signed.  Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
  • Page 10: Specifications

    3. Specifications Indoor CS-Z25UD3EAW CS-Z35UD3EAW Model Outdoor CU-Z25UBEA CU-Z35UBEA Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 2.50 3.20 0.85 3.50 4.00 Capacity BTU/h 2900 8530 10900 2900...
  • Page 11 Indoor CS-Z25UD3EAW CS-Z35UD3EAW Model Outdoor CU-Z25UBEA CU-Z35UBEA Type Hermetic Motor (Rotary) Hermetic Motor (Rotary) Compressor Motor Type Brushless (6 poles) Brushless (6 poles) Output Power Type SIROCCO SIROCCO Material GFZ010A / GF20 GFZ010A / GF20 Motor Type DC / Transistor (8-poles)
  • Page 12 Indoor CS-Z25UD3EAW CS-Z35UD3EAW Model Outdoor CU-Z25UBEA CU-Z35UBEA Weight Net (I/D / O/D) kg (lb) 19 (42) / 33 (73) 19 (42) / 35 (77) Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)
  • Page 13 Indoor CS-Z50UD3EAW CS-Z60UD3EAW Model Outdoor CU-Z50UBEA CU-Z60UBEA Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.90 5.10 5.70 0.90 6.00 6.50 Capacity BTU/h 3070 17400 19400 3070 20500 22200 Kcal/h 4390 4900...
  • Page 14 Indoor CS-Z50UD3EAW CS-Z60UD3EAW Model Outdoor CU-Z50UBEA CU-Z60UBEA Type Hermetic Motor (Rotary) Hermetic Motor (Rotary) Compressor Motor Type Brushless (4 poles) Brushless (4 poles) Output Power Type SIROCCO SIROCCO Material GFZ010A / GF20 GFZ010A / GF20 Motor Type DC / Transistor (8-poles) DC / Transistor (8-poles) Input Power –...
  • Page 15 Indoor CS-Z50UD3EAW CS-Z60UD3EAW Model Outdoor CU-Z50UBEA CU-Z60UBEA Weight Net (I/D / O/D) kg (lb) 19 (42) / 43 (95) 19 (42) / 43 (95) Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 12.70 (1/2) Standard length m (ft) 5.0 (16.4)
  • Page 16 (as shown in the table above) Example: The indoor units’ combination below is possible to connect to CU-3Z68TBE. (Total nominal capacity of indoor units is between 4.5kW to 11.2kW) 1) Two CS-Z25UD3EAW only. (Total nominal cooling capacity is 5.0kW)
  • Page 17 (as shown in the table above) Example: The indoor units’ combination below is possible to connect to CU-4Z80TBE. (Total nominal capacity of indoor units is between 4.5kW to 14.7kW) 1) Two CS-Z25UD3EAW only. (Total nominal cooling capacity is 5.0kW)
  • Page 18 Example: The indoor units’ combination below is possible to connect to CU-3E23SBE. (Total nominal capacity of indoor units is between 4.5kW to 11.0kW) 1) Two CS-Z25UD3EAW only. (Total nominal cooling capacity is 5.0kW) Note*: Above outdoor unit is contains and operates with refrigerant R410A gas.
  • Page 19 Example: The indoor units’ combination below is possible to connect to CU-4E27PBE. (Total nominal capacity of indoor units is between 4.5kW to 13.6kW) 1) Two CS-Z25UD3EAW only. (Total nominal cooling capacity is 5.0kW) Note*: Above outdoor unit is contains and operates with refrigerant R410A gas.
  • Page 20: Features

    4. Features  Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control  Environment Protection Non-ozone depletion substances refrigerant (R32)  Long Installation Piping Long piping up to 20 meters (1.0 ~ 1. 5HP) and 30 meters (2.0 ~ 2.25HP) during single split connection only ...
  • Page 21: Location Of Controls And Components

    5. Location of Controls and Components Indoor Unit Air inlet Air outlet Outdoor Unit Remote Control Timer/Clock Setting Display Fan Speed Display Temperature Setting Display Quiet Operation Indicator Operation Mode Selection Powerful Operation Indicator Indicator System Error Display OFF Indicator OFF/ON Button OFF / ON Operation LED...
  • Page 22: Dimensions

    Indoor Unit <Front View> (AIR OUTLET DUCT FLANGE) <Top View> <Side View> 160 × 4 = 640 <Side View> WATER INLET DRAIN PORT (UPPER & LOWER) <Back View> <Remote Control> <Remote control transmitter> 15.5 (AIR INLET) AIR FILTER Panasonic Unit: mm...
  • Page 23: Outdoor Unit

    Outdoor Unit 6.2.1 CU-Z25UBEA <Top View> Space necessary for installation 67.6 (104.7) 570.3 104.9 60.5 100 mm 100 mm 1000 mm 2-way valve at Liquid side Anchor Bolt Pitch (High Pressure) × 3-way valve at Gas side (Low Pressure) <Side View> <Side View>...
  • Page 24 6.2.3 CU-Z50UBEA CU-Z60UBEA <Top View> Space necessary for installation (131) 34.7 100 mm 100 mm 1000 mm Anchor Bolt Pitch 360.5 × 613 2-way valve at Liquid side (High Pressure) 3-way valve at Gas side (Low Pressure) <Front View> <Side View> <Side View>...
  • Page 25: Refrigeration Cycle Diagram

    7. Refrigeration Cycle Diagram CS-Z25UD3EAW CU-Z25UBEA CS-Z35UD3EAW CU-Z35UBEA INDOOR OUTDOOR LIQUID EXPANSION TEMP. SIDE STRAINER VALVE STRAINER SENSOR 2-WAY VALVE PIPE TEMP. INTAKE SENSOR 2 TEMP. SENSOR CONDENSER PIPE TEMP. PIPE SENSOR 1 TEMP. SENSOR HEAT EXCHANGER (EVAPORATOR) SIDE MUFFLER...
  • Page 26: Cs-Z50Ud3Eaw Cu-Z50Ubea Cs-Z60Ud3Eaw Cu-Z60Ubea

    CS-Z50UD3EAW CU-Z50UBEA CS-Z60UD3EAW CU-Z60UBEA INDOOR OUTDOOR LIQUID EXPANSION SIDE STRAINER VALVE 2-WAY PROCESS VALVE TUBE TEMP. PIPE SENSOR TEMP. CONDENSER INTAKE SENSOR 2 TEMP. SENSOR PIPE TEMP. PIPE SENSOR 1 TEMP. SENSOR HEAT EXCHANGER (EVAPORATOR) SIDE 4-WAYS VALVE 3-WAY RECEIVER VALVE TANK SENSOR...
  • Page 27: Block Diagram

    8. Block Diagram CS-Z25UD3EAW CU-Z25UBEA CS-Z35UD3EAW CU-Z35UBEA...
  • Page 28: Cs-Z50Ud3Eaw Cu-Z50Ubea Cs-Z60Ud3Eaw Cu-Z60Ubea

    CS-Z50UD3EAW CU-Z50UBEA CS-Z60UD3EAW CU-Z60UBEA...
  • Page 29: Wiring Connection Diagram

    9. Wiring Connection Diagram Indoor Unit...
  • Page 30: Outdoor Unit

    Outdoor Unit 9.2.1 CU-Z25UBEA CU-Z35UBEA YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL...
  • Page 31 9.2.2 CU-Z50UBEA CU-Z60UBEA YELLOW (YLW) OR (C) REMARKS BLU: BLUE TO INDOOR UNIT BLK: BLACK SINGLE PHASE BLUE (BLK) (WHT) (RED) WHT: WHITE POWER SUPPLY (BLU) (RED) RED: RED OR (R) OR (S) YLW: YELLOW TERMINAL GRY: GRAY (TRADEMARK) REACTOR BOARD GRN: GREEN COMPERSSOR TERMINAL...
  • Page 32: Electronic Circuit Diagram

    10. Electronic Circuit Diagram 10.1 Indoor Unit...
  • Page 33: Outdoor Unit

    10.2 Outdoor Unit 10.2.1 CU-Z25UBEA CU-Z35UBEA REACTOR RAT1 RAT2 (GRY) (GRY) 15.8k 220u SINGLE PHASE POWER SUPPLY TO INDOOR UNIT OUTDOOR AIR TEMP. SENSOR (THERMISTOR) t° TERMINAL CN–TH1 t° BOARD (WHT) PIPING TEMP. SENSOR (THERMISTOR) DATA t° (RED) COMMUNICATION COMPRESSOR TEMP. SENSOR (THERMISTOR) CN–TANK CIRCUIT 4.99k...
  • Page 34 10.2.2 CU-Z50UBEA CU-Z60UBEA TO INDOOR UNIT SINGLE PHASE (BLK) (WHT) (RED) POWER SUPPLY TERMINAL BOARD REACTOR RAT2 RAT1 DATA (GRY) (GRY) (RED) COMMUNICATION NOISE FILTER CIRCUIT FUSE 5 AC-BLK CIRCUIT (20A 250V) 15.8k (BLK) 470u FUSE 1 (25A 250V) FUSE 8 FUSE 6 OUTDOOR AIR TEMP.
  • Page 35: Printed Circuit Board

    11. Printed Circuit Board 11.1 Indoor Unit 11.1.1 Main Printed Circuit Board CN-T1 CN-AC CN-T2 CN-DRMTR1 JP10 (Random Auto Restart enable/disable) CN-FM CN-TH HAJEM-A CN-CNT CN-FSW CN-DISP...
  • Page 36: Outdoor Unit

    11.2 Outdoor Unit 11.2.1 Main Printed Circuit Board 11.2.1.1 CU-Z25UBEA CU-Z35UBEA POWER TRANSISTOR (IPM) CN-MTR2 CN-MTR1 CN-TH1 CN-DEMAND CN-TANK CN-HOT CN-STM AC-WHT DATA CURRENT TRANSFORMER (CT) AC-BLK CN-V1...
  • Page 37 11.2.1.2 CU-Z50UBEA CU-Z60UBEA POWER TRANSISTOR (IPM) CN-MTR2 CURRENT TRANSFORMER (CT) CN-MTR1 CN-STM1 CN-TH1 CN-HOT DATA CN-TANK AC-WHT AC-BLK...
  • Page 38: Installation Instruction

    12. Installation Instruction ■ Required Materials Insulation of piping connections  Read the catalog and other technical materials • Carry out insulation after and prepare the required materials. checking for gas leaks and secure with vinyl tape.  Applicable piping kit Vinyl tape Piping size Applicable piping kit...
  • Page 39: Indoor Unit

    12.1 Indoor Unit 12.1.1 Selecting the Installation Location Take into consideration the following contents when creating the blueprint. ■ Indoor unit installation location  Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. ...
  • Page 40 12.1.3 Installing the Indoor Unit (Installation Embedded in the Ceiling) 12.1.3.1 Preparation before installation  Always provide sufficient entry and exit space to allow installation work, inspection and unit replacement.  Waterproof the rear surface of the ceiling below the unit in consideration of water droplets forming and dropping. CAUTION When cooling operation is performed for an extended period under the following conditions, water droplets may form and drop.
  • Page 41 Dimension of the indoor unit 692 (Flange for air outlet duct) 640 (160x4) 2-ø3.1(Hole) 5-ø3.1(Hole) Inspection access (450x450) (Field supply) 824 (Suspension bolt pitch) 10-ø3.1(Hole) * Filter Uninstalled In case of Bottom Intake Dummy hole Air intake Remove the frame filter assy as shown in Cover plate diagram 1 Remove cover plate as shown in diagram 1...
  • Page 42 Ceiling Opening  Install inspection opening (450 mm x 450 mm) on the control box side where maintenance and inspection of the control box and drain pump are easy. Install another inspection opening (800 mm x 700 mm) also at the lower part of the unit.
  • Page 43 Installation into the Ceiling  Attach the nuts and washers to the hanging bolts, then lift up and hook the main unit onto the hanging fixtures.  Check if the unit is leveled using a level or a vinyl hose filled partially with water. Hanging bolt (M10) (locally purchased) Flat...
  • Page 44 Embed an outlet box (JIS C 8336) into the wall. Outlet box maybe purchased separately. Medium size square outlet box (obtain locally) Part No. DS3744 (Panasonic Co., Ltd.) or equivalent. Secure the remote controller lower case to the outlet box with the two accessory screws 3. Make sure that the lower case is flat againts the wall at this time, with no bending.
  • Page 45 12.1.4 Connecting the Drain Piping  Lay the drain piping so as to ensure drainage.  Use a locally purchased VP20 general rigid PVC pipe (outer diameter ø26) for the drain piping and firmly connect the indoor unit and the drain piping using supplied hose band to ensure that no leakage occurs. ...
  • Page 46 12.1.6 Connecting the Indoor/Outdoor Connection Cable   Remove the control box cover and insert the Ensure the colour of wires of outdoor unit and the connection cable into the control box. terminal Nos. are the same to the indoor’s ...
  • Page 47 12.1.6.1 Wire Stripping and Connecting Requirement Wire stripping Conductor not Conductor Conductor fully inserted fully inserted over inserted Indoor/outdoor connection terminal board 5 mm or more No loose strand ACCEPT PROHIBITED PROHIBITED (gap between wires) when inserted Do not joint wires WARNING RISK OF FIRE JOINING OF WIRES MAY CAUSE...
  • Page 48 12.1.7.2 Connecting the Piping to Outdoor Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align center of piping to valve and then tighten with torque wrench to the specified torque as stated in the table.
  • Page 49: Outdoor Unit

    12.2 Outdoor Unit 12.2.1 Select the Best Location  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.  There should not be any animal or plant which could be affected by hot air discharged. ...
  • Page 50 12.2.2 Install the Outdoor Unit  After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
  • Page 51 12.2.4 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Liquid side Indoor unit Outdoor unit Two-way valve Closed Gas side Three-way valve Closed Vacuum CLOSE pump...
  • Page 52 12.2.5 Connect the Cable to the Outdoor Unit (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) Remove the control board cover from the unit by loosening the screw. Cable connection to the power supply through Isolating Devices (Disconnecting means). Connect approved type polychloroprene sheathed power supply cord 3 x 1.5 mm (1.0 ~ 1.5HP) or 3 x 2.5 mm (2.0 ~ 2.25HP) type designation 60245 IEC 57 or heavier cord to the terminal board, and...
  • Page 53 12.2.7 Cutting and Flaring the Piping Please cut using pipe cutter and then remove the burrs. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. Please make flare after inserting the flare nut onto the copper pipes.
  • Page 54: Installation And Servicing Air Conditioner Using R32

    13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
  • Page 55 2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
  • Page 56: Refrigerant Piping Installation • Tools Used In Services

    13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
  • Page 57 3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
  • Page 58 7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
  • Page 59 11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
  • Page 60: New Installation, Relocation, Repairing Of Refrigerant Cycle System The Procedures

    13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
  • Page 61: Piping Installation Of R32

    13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
  • Page 62: Installation, Relocation, And Service

    13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
  • Page 63 13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
  • Page 64 13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
  • Page 65 13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
  • Page 66: Repairing Of Refrigerant Cycle / Brazing Point

    13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
  • Page 67 2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
  • Page 68 13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
  • Page 69 13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
  • Page 70 13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
  • Page 71 (Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
  • Page 72: Reference> Analysis Method For No Error Code, No Cooling / No Warming

    13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
  • Page 73 1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
  • Page 74: Operation And Control

    14. Operation and Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
  • Page 75 14.1.4 Heating Operation 14.1.4.1 Thermostat control  Compressor is OFF when Intake Air Temperature - Internal Setting Temperate > +2.0°C.  Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF point. 14.1.5 Automatic Operation ...
  • Page 76  The indoor fan will operate according to pattern below. [Heating]  According to indoor pipe temperature, automatic heating fan speed is determined as follows. B. Feedback control  Immediately after the fan motor started, feedback control is performed once every second. ...
  • Page 77: Quiet Operation (Cooling Mode/Cooling Area Of Soft Dry Mode)

    14.2 Quiet Operation (Cooling Mode/Cooling area of Soft Dry Mode) A. Purpose To provide quiet cooling operation compare to normal operation. B. Control condition a. Quiet operation start condition  When “quiet” button at remote control is pressed. b. Quiet operation stop condition When one of the following conditions is satisfied, quiet operation stops: Powerful button is pressed.
  • Page 78: Powerful Mode Operation

    14.3 Powerful Mode Operation When the powerful mode is selected, the internal setting temperature will shift higher up to +6.0°C (for Heating) or lower up to 4°C (for Cooling/Soft Dry) than remote control setting temperature for 20 minutes to achieve the setting temperature quickly.
  • Page 79: Ha Terminal (Hajem-A)

    14.7 HA Terminal (HAJEM-A)  Enable digital connection from indoor unit to external devices.  Control items: Start/stop input. Start/stop signal output. 200~300msec ON/OFF input (Pin 1-2) Monitor output (Pin 3-4) Unit condition  Condition 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal. (1 pulse signal: shortage status 200~300msec) 3-4 (Static output): 5V output during the unit ON.
  • Page 80 14.7.1 Drain Pump Control  This unit has built-in with drain pump. Control content  During COOL/DRY mode. During COOL/DRY mode, drain pump starts 10 seconds after indoor fan motor starts. The drain pump turns ON and turns OFF periodically. (ON or OFF duration depends on room temperature). ...
  • Page 81: Operation Control (For Multi Split Connection)

    15. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in this chapter. 15.1 Cooling operation 15.1.1 Thermostat control  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature <...
  • Page 82: Automatic Operation

    15.4 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake and outdoor air temperature.  During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature.
  • Page 83: Protection Control

    16. Protection Control 16.1 Protection Control for All Operations 16.1.1 Restart Control (Time Delay Safety Control)  The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
  • Page 84 16.1.4 Compressor Overheating Prevention Control  Instructed frequency for compressor operation will be regulated by compressor temperature. The changes of frequency are as below.  If compressor temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes (“F97”...
  • Page 85: Protection Control For Cooling & Soft Dry Operation

    16.2 Protection Control for Cooling & Soft Dry Operation 16.2.1 Outdoor Air Temperature Control  The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.  This control will begin 1 minute after the compressor starts. ...
  • Page 86: Protection Control For Heating Operation

    16.2.5 Dew Prevention Control 1  To prevent dew formation at indoor unit discharge area.  This control will be activated if: Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled. When Cooling or Dry mode is operated more than 20 minutes or more. ...
  • Page 87 16.3.4 Low Temperature Compressor Oil Return Control  In heating operation, if the outdoor temperature falls below -10°C when compressor starts, the compressor frequency will be regulated up to 600 seconds. 16.3.5 Cold Draught Prevention Control  When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced. 16.3.6 Deice Operation ...
  • Page 88: Servicing Mode

    17. Servicing Mode 17.1 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)  The Test Run operation will be activated by short-circuiting CN-S (Pin 1 & 2) at outdoor unit PCB after power supplied to outdoor unit terminal 1 and 2. The unit forced to run rated frequency cooling operation mode. 17.1.1 CU-Z25UBEA CU-Z35UBEA POWER...
  • Page 89 17.1.2 CU-Z50UBEA CU-Z60UBEA POWER TRANSISTOR (IPM) CN-S CN-MTR2 CURRENT TRANSFORMER (CT) CN-MTR1 CN-STM1 CN-TH1 CN-HOT DATA CN-TANK AC-WHT AC-BLK...
  • Page 90: Troubleshooting Guide

    18. Troubleshooting Guide 18.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air Temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
  • Page 91 18.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
  • Page 92: Breakdown Self Diagnosis Function

    18.2 Breakdown Self Diagnosis Function 18.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  Once abnormality has occurred during operation, the unit will stop its operation, and OFF/ON operation LED OFF.  OFF indicator does not shown on remote control display. ...
  • Page 93: Error Codes Table

    18.3 Error Codes Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only  Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
  • Page 94 Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation  Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality  Expansion valve and lead wire and connector Outdoor high High pressure sensor open...
  • Page 95: Self-Diagnosis Method

    18.4 Self-diagnosis Method 18.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions  During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused  Faulty indoor unit PCB.
  • Page 96 18.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions  During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit or outdoor unit PCBs mounted. ...
  • Page 97 18.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 98 18.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.  Faulty sensor.
  • Page 99 18.4.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions  An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused  Lack of gas  Broken CT (current transformer) ...
  • Page 100 18.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm) Malfunction Caused ...
  • Page 101 18.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 102 18.4.8 H24 (Indoor Pipe Temperature Sensor 2 Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 2 are used to determine sensor errors. Malfunction Caused  Faulty connector connection.
  • Page 103 18.4.9 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 104 18.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 105 18.4.11 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 106 18.4.12 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.
  • Page 107 18.4.13 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions  The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit and outdoor unit PCBs used.  Indoor unit or outdoor unit PCB defective.
  • Page 108 18.4.14 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 109 18.4.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 110 18.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused  Operation stops due to short circuit inside the fan motor winding. ...
  • Page 111 18.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions  Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
  • Page 112 18.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) Malfunction Caused ...
  • Page 113 18.4.19 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
  • Page 114 18.4.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
  • Page 115 18.4.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions  To maintain DC voltage level supply to power transistor.  To detect high DC voltage level after rectification. Malfunction Caused  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
  • Page 116 18.4.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions  The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused  Lack of gas.  3-way valve close. Troubleshooting...
  • Page 117 18.4.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions  A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused  Compressor terminal disconnect  Faulty Outdoor PCB  Faulty compressor Troubleshooting...
  • Page 118 18.4.24 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions  During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
  • Page 119 18.4.25 F96 (IPM Overheating) Malfunction Decision Conditions  During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature sensor. Multi Models only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
  • Page 120 18.4.26 F97 (Compressor Overheating) Malfunction Decision Conditions  During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused  Faulty compressor tank temperature sensor  2/3 way valve closed ...
  • Page 121 18.4.27 F98 (Input Over Current Detection) Malfunction Decision Conditions  During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
  • Page 122 18.4.28 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused  DC current peak due to compressor failure. ...
  • Page 123: Disassembly And Assembly Instructions

    19. Disassembly and Assembly Instructions WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 19.1 Indoor Electronic Controller, Blower Fan, Fan Motor &...
  • Page 124 19.1.3 To Remove Fan Motor and Blower Fan Detach the Upper and Inner Casing Disengage the 4 catches (2 each on the left and right) on the Air Guide. Air guide (Upper) Air guide (Upper) Catches Air guide (Bottom) Air guide (Bottom) Unscrew the 2 screws on the Fan Motor Bracket and detach Fan Motor Bracket.
  • Page 125 Unscrew 5 screws on the Evaporator and remove 2 sensor from holder and remove Evaporator from the unit. Remove Screw Remove Sensor Unscrew 4 screws, 1 nut and 1 Spring Clip on the Drain Motor Bracket and remove Drain Motor from unit. Spring Clip Remove Screw Remove Nut...
  • Page 126: Outdoor Electronic Controller Removal Procedure

    19.2 Outdoor Electronic Controller Removal Procedure 19.2.1 CU-Z25UBEA Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
  • Page 127 19.2.2 CU-Z35UBEA Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Fig. 4 Fig. 1 Remove the 8 screws of the Front Panel. Fig. 2 Fig.
  • Page 128 19.2.3 CU-Z50UBEA CU-Z60UBEA Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws Screws Fig.
  • Page 129: Technical Data

    20.1 Cool Mode Performance Data Unit setting: Standard piping length, Hi Fan, Cool mode at 16°C Voltage: 230V 20.1.1 CS-Z25UD3EAW CU-Z25UBEA Indoor (°C) Outdoor DB (°C) 19.0 2451 2402 514 2770 2659 529 3058 2817 510 3155 2837 451 3268 2702 345 2635 2403 527 2500 2280 580 22.0 2861 2133 594 2903 1850 481 2730 1686 566 2741 1735 588 2861 2009 548 2996 1922 648 3001 1925 583...
  • Page 130 20.1.4 CS-Z60UD3EAW CU-Z60UBEA Indoor (°C) Outdoor DB (°C) 19.0 7335 4728 1573 7398 4737 1461 7268 4704 1558 7354 4735 1465 7214 4604 1465 3467 3037 538 6000 4210 2040 22.0 7954 3748 1589 8220 3799 1345 8199 3791 1264 8108 3741 1459 7988 3710 1451 6029 3086 1142 6235 3146 2185 15.7 5952 4524 1403 6167 4385 1188 6012 4311 1086 6784 4636 1434 6394 4450 1290 3465 2942 630 5035 3902 2020 18.4 7408 3739 1340 7185 3697 1564 7119 3674 1628 7072 3650 1587 8332 4163 1807 5404 2469 1091 5702 3255 2033 13.3 4598 3718 935 4646 3739 940 4860 3841 826 4522 3637 952 4991 3882 973 3463 3003 722 4214 3523 2030...
  • Page 131: Heat Mode Performance Data

    20.2 Heat Mode Performance Data Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C Voltage: 230V 20.2.1 CS-Z25UD3EAW CU-Z25UBEA Indoor (°C) Outdoor WB (°C) 2379 1181 2155 1138 2846 1048 3028 3714 2380 1040 2600 1200 3330 1110...
  • Page 132: Fan Performance

    20.3 Fan Performance 20.3.1 CS-Z25UD3EAW Test Report Static Pressure Airflow Static Pressure Airflow (Pa) /min) (Pa) /min) -0.1 10.37 13.10 10.09 14.2 11.66 14.4 8.45 26.0 10.37 23.4 6.89 35.2 9.12 30.4 5.54 43.5 7.98 37.1 4.35 49.1 6.97 52.7 6.13...
  • Page 133 20.3.2 CS-Z35UD3EAW Test Report Static Pressure Airflow Static Pressure Airflow (Pa) /min) (Pa) /min) 13.58 -0.1 10.37 10.09 15.3 12.09 14.4 8.45 28.0 10.74 23.4 6.89 37.9 9.45 30.4 5.54 46.7 8.27 37.1 4.35 52.7 7.23 -0.1 11.97 56.6 6.35 11.04 58.5 5.41...
  • Page 134 20.3.3 CS-Z50UD3EAW Test Report Static Pressure Airflow Static Pressure Airflow (Pa) /min) (Pa) /min) 17.15 -0.1 11.08 10.78 24.4 15.27 16.4 9.02 44.6 13.57 26.7 7.36 60.4 11.94 34.7 5.92 74.5 10.45 42.4 4.65 84.1 9.13 -0.1 14.10 90.3 8.02 10.7 13.01 93.4...
  • Page 135 20.3.4 CS-Z60UD3EAW Test Report Static Pressure Airflow Static Pressure Airflow (Pa) /min) (Pa) /min) 17.63 -0.1 11.55 11.24 25.8 15.69 17.8 9.41 47.1 13.95 29.0 7.67 63.8 12.27 37.7 6.17 78.7 10.74 46.1 4.85 88.8 9.38 -0.1 14.57 95.4 8.24 11.4 13.45 98.7...
  • Page 136: Service Data

    Condition Indoor room temperature: 27°C Dry Bulb/19°C Wet Bulb Unit setting: Standard piping length, forced cooling at 16°C, Hi fan Compressor frequency: Rated for cooling operation Piping length: 5m Voltage: 230V 21.1.1 CS-Z25UD3EAW CU-Z25UBEA 18.00 17.00 16.00 15.00 14.00 13.00 12.00...
  • Page 137 21.1.2 CS-Z35UD3EAW CU-Z35UBEA 16.00 15.00 14.00 13.00 12.00 11.00 10.00 9.00 8.00 Outdoor Air Temperature (°C) 5.00 4.50 4.00 3.50 3.00 2.50 2.00 Outdoor Air Temperature (°C) 1.20 1.00 0.80 0.60 Outdoor Air Temperature (°C)
  • Page 138 21.1.3 CS-Z50UD3EAW CU-Z50UBEA 16.00 15.00 14.00 13.00 12.00 11.00 10.00 9.00 8.00 Outdoor Air Temperature (°C) 8.00 7.50 7.00 6.50 6.00 5.50 5.00 4.50 4.00 Outdoor Air Temperature (°C) 1.10 0.90 0.70 Outdoor Air Temperature (°C)
  • Page 139 21.1.4 CS-Z60UD3EAW CU-Z60UBEA 14.00 13.00 12.00 11.00 10.00 9.00 8.00 Outdoor Air Temperature (°C) 11.00 10.00 9.00 8.00 7.00 6.00 5.00 4.00 Outdoor Air Temperature (°C) 1.20 1.00 0.80 0.60 Outdoor Air Temperature (°C)
  • Page 140: Heat Mode Outdoor Air Temperature Characteristic

    Indoor room temperature: 20°C Dry Bulb/ -°C Wet Bulb Unit setting: Standard piping length, forced heating at 30°C, Hi fan Compressor frequency: Rated for Heating operation Piping length: 5m Voltage: 230V 21.2.1 CS-Z25UD3EAW CU-Z25UBEA Outdoor Air Temperature (°C) 5.00 4.00 3.00 2.00 1.00...
  • Page 141 21.2.2 CS-Z35UD3EAW CU-Z35UBEA Outdoor Air Temperature (°C) 6.00 5.00 4.00 3.00 2.00 1.00 Outdoor Air Temperature (°C) Outdoor Air Temperature (°C)
  • Page 142 21.2.3 CS-Z50UD3EAW CU-Z50UBEA Outdoor Air Temperature (°C) 10.00 9.50 9.00 8.50 8.00 7.50 7.00 6.50 6.00 5.50 5.00 4.50 4.00 Outdoor Air Temperature (°C) Outdoor Air Temperature (°C)
  • Page 143 21.2.4 CS-Z60UD3EAW CU-Z60UBEA Outdoor Air Temperature (°C) 11.00 10.00 9.00 8.00 7.00 6.00 5.00 4.00 Outdoor Air Temperature (°C) Outdoor Air Temperature (°C)
  • Page 144: Piping Length Correction Factor

    21.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 21.3.1 CS-Z25UD3EAW CU-Z25UBEA Cooling Capacity 1.10 1.0096 1.0000 0.9781 1.00 0.9628 0.90 9 10 11 12 13 14 15 16 17 18 19 20 21...
  • Page 145 21.3.2 CS-Z35UD3EAW CU-Z35UBEA Cooling Capacity 1.10 1.0080 1.0000 0.9850 1.00 0.9656 0.90 9 10 11 12 13 14 15 16 17 18 19 20 21 Pipe Length (m) Heating Capacity 1.10 1.0118 1.0000 0.9800 1.00 0.9392 0.90 0.80 9 10 11 12 13 14 15 16 17 18 19 20 21 Pipe Length (m) Note: The graphs show the factor after added right amount of additional refrigerant.
  • Page 146 21.3.3 CS-Z50UD3EAW CU-Z50UBEA CS-Z60UD3EAW CU-Z60UBEA Cooling Capacity 1.10 1.0080 1.0000 0.9895 1.00 0.9656 0.9418 0.90 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Pipe Length (m) 1.10 Heating Capacity...
  • Page 147: Exploded View And Replacement Parts List

    22. Exploded View and Replacement Parts List 22.1 Indoor Unit Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 148 SAFETY REF NO. PART NAME & DESCRIPTION QTY. CS-Z25UD3EAW CS-Z35UD3EAW REMARK CABINET TOP PLATE - COMPLETE CWE03C1169 ← FOAMED STYRENE COMPLETE CWG07C1094 ← FOAMED STYRENE COMPLETE CWG07C1089 ← FOAMED STYRENE COMPLETE CWG07C1090 ← BULKHEAD CWD531059 ← CABINET SIDE PLATE - COMPLETE CWE04C1565 ←...
  • Page 149 SAFETY REF NO. PART NAME & DESCRIPTION QTY. CS-Z25UD3EAW CS-Z35UD3EAW REMARK INSTALLATION INSTRUCTION ACXF60-26290 ← INSTALLATION INSTRUCTION ACXF60-26300 ← INSTALLATION INSTRUCTION ACXF60-26310 ← INSTALLATION INSTRUCTION ACXF60-26320 ← INSTALLATION INSTRUCTION ACXF60-26330 ← INSTALLATION INSTRUCTION ACXF60-26340 ← INSTALLATION INSTRUCTION ACXF60-26350 ← INSTALLATION INSTRUCTION ACXF60-26360 ←...
  • Page 150 SAFETY REF NO. PART NAME & DESCRIPTION QTY. CS-Z50UD3EAW CS-Z60UD3EAW REMARK CABINET TOP PLATE - COMPLETE CWE03C1169 ← FOAMED STYRENE COMPLETE CWG07C1094 ← FOAMED STYRENE COMPLETE CWG07C1089 ← FOAMED STYRENE COMPLETE CWG07C1090 ← BULKHEAD CWD531059 ← CABINET SIDE PLATE - COMPLETE CWE04C1565 ←...
  • Page 151 SAFETY REF NO. PART NAME & DESCRIPTION QTY. CS-Z50UD3EAW CS-Z60UD3EAW REMARK INSTALLATION INSTRUCTION ACXF60-26290 ← INSTALLATION INSTRUCTION ACXF60-26300 ← INSTALLATION INSTRUCTION ACXF60-26310 ← INSTALLATION INSTRUCTION ACXF60-26320 ← INSTALLATION INSTRUCTION ACXF60-26330 ← INSTALLATION INSTRUCTION ACXF60-26340 ← INSTALLATION INSTRUCTION ACXF60-26350 ← INSTALLATION INSTRUCTION ACXF60-26360 ←...
  • Page 152: Outdoor Unit

    22.2 Outdoor Unit 22.2.1 CU-Z25UBEA Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 153 ACXB00-00130 V-COIL COMPLETE (4-WAY VALVE) ACXA43C00250 WIRE NET ACXD04-00040A BAG - COMPLETE CWG87C900 V-COIL COMPLETE (EXP. VALVE) ACXA43C00640 STRAINER CWB111032 RECEIVER CWB14011 PANASONIC BADGE CWE373439 INSTALLATION INSTRUCTION ACXF60-27460 INSTALLATION INSTRUCTION ACXF60-27470 INSTALLATION INSTRUCTION ACXF60-27480 INSTALLATION INSTRUCTION ACXF60-27490 INSTALLATION INSTRUCTION ACXF60-27500...
  • Page 154 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z25UBEA REMARK INSTALLATION INSTRUCTION ACXF60-27510 INSTALLATION INSTRUCTION ACXF60-27520 INSTALLATION INSTRUCTION ACXF60-27530 INSTALLATION INSTRUCTION ACXF60-27540 INSTALLATION INSTRUCTION ACXF60-27550 INSTALLATION INSTRUCTION ACXF60-27560 INSTALLATION INSTRUCTION ACXF60-27570 INSTALLATION INSTRUCTION ACXF60-27580 INSTALLATION INSTRUCTION ACXF60-27590 INSTALLATION INSTRUCTION ACXF60-27600 CWG861078 BASE BOARD - COMPLETE CWG62C1223...
  • Page 155 22.2.2 CU-Z35UBEA Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 156 4-WAYS VALVE ACXB00-00130 V-COIL COMPLETE (4 WAY VALVE) ACXA43C00250 WIRE NET CWD041200A V-COIL COMPLETE (EXP. VALVE) ACXA43C00640 RECEIVER CWB14011 STRAINER CWB111032 PANASONIC BADGE CWE373439 BAG - COMPLETE CWG87C900 SOUND PROOF MATERIAL CWG302701 INSTALLATION INSTRUCTION ACXF60-27460 INSTALLATION INSTRUCTION ACXF60-27470 INSTALLATION INSTRUCTION ACXF60-27480...
  • Page 157 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z35UBEA REMARK INSTALLATION INSTRUCTION ACXF60-27530 INSTALLATION INSTRUCTION ACXF60-27540 INSTALLATION INSTRUCTION ACXF60-27550 INSTALLATION INSTRUCTION ACXF60-27560 INSTALLATION INSTRUCTION ACXF60-27570 INSTALLATION INSTRUCTION ACXF60-27580 INSTALLATION INSTRUCTION ACXF60-27590 INSTALLATION INSTRUCTION ACXF60-27600 ACXG86-03760 BASE BOARD - COMPLETE CWG62C1144 SHOCK ABSORBER (L) CWG713416 SHOCK ABSORBER (R)
  • Page 158 22.2.3 CU-Z50UBEA CU-Z60UBEA Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 159 WIRE NET ACXD04-00130A ← CABINET TOP PLATE ACXE03-00170A ← CONTROL BOARD COVER - COMPLETE ACXH13C00170 ← CONTROL BOARD COVER CWH131470 ← PANASONIC BADGE CWE373439 ← SOUND PROOF MATERIAL CWG302636 ← SOUND PROOF MATERIAL CWG302630 ← RECEIVER CWB14011 ← SOUND PROOF MATERIAL CWG302632 ←...
  • Page 160 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z50UBEA CU-Z60UBEA REMARK INSTALLATION INSTRUCTION ACXF60-27520 ← INSTALLATION INSTRUCTION ACXF60-27530 ← INSTALLATION INSTRUCTION ACXF60-27540 ← INSTALLATION INSTRUCTION ACXF60-27550 ← INSTALLATION INSTRUCTION ACXF60-27560 ← INSTALLATION INSTRUCTION ACXF60-27570 ← INSTALLATION INSTRUCTION ACXF60-27580 ← INSTALLATION INSTRUCTION ACXF60-27590 ←...