5 Registe r List :
In GXE, Input Register and Holding Register of 16-bit data are used in the data model specified by MODBUS protocol.
Discrete Register and Coil Register of 1 bit data are not used.
T he register address of GXE in this communication manual is indicated by the PDU address.
If a register that does not exist is used as the starting address, it becomes an exception response.
For details, please refer to the communication manual.
・ Numerical notation
Numbers starting with '0x' indicate hexadecimal numbers. (Example : 0x0400 = 1024d)
Decimal numbers are indicated by appending 'd' after the value or without adding anything. (Example : 1024d , 1024)
Binary numbers are indicated by appending '0b' before the value. (Example : 0b0100 0000 0000 = 1024d)
T he internal data type of GXE is 16 bit little endian. ( LSB: bit 0 / MSB: bit 15 )
・ Representation of function name
T his document has prioritized the use of common names so far. However, GXE unique name is used in the register list.
T he correspondence is as follows and the meaning is the same.
Common names
RC
CV
5.1 Input Registers
Input Registers are read-only 16-bit data registers.
Mainly, Input Registers has measurement data.
Input Register
#
1
Alarm History
2
Output Voltage
3
Output Current
4
T emperature
5
Operation T ime
6
E-Cap L0 Remaining
7
Model Name
8
Serial No.
9
Lot No.
10
FW Version
GXE unique name
(Remote Control)
CNT
(Constant Voltage)
PV
Starting Address
Qty.
0 (0x0000)
1
Indicates protection content that occurred.
1 (0x0001)
1
T he value of the output voltage (between + S and -S terminals)
is indicated in normalized signed Q10 format.
2 (0x0002)
1
T he output current value is indicated in normalized signed Q10 format.
3 (0x0003)
1
T he measured value of GXE internal temperature is indicated.
4 (0x0004)
2
T he cumulative operating time of the power supply is indicated.
6 (0x0006)
1
Among the electrolytic capacitors inside the power supply,
the predicted lifetime value of the most degraded capacitor is indicated.
T he mounting direction of power supply is assumed to be "Mount A"
Please use as a guide only.
500 (0x01F4)
15 T he model name registered in the product is indicated.
520 (0x0208)
8
T he serial No. registered in the product is indicated.
540 (0x021C)
8
T he lot No. registered in the product is indicated.
1000 (0x03E8)
1
T he firmware version registered in the product is indicated.
<Page>
34/41
(Abbreviation for "Control")
(Programmable Voltage)
Function
bit
Name
Overview
0
SWOCP Indicates that output overcurrent has been
detected.
1
HWOCP
2
SWOVP Indicates that output overvoltage was
detected.
3
HWOVP
Indicates that overtemperature
4
OT P
protection has been activated.
Indicates that the booster output
5
PFCLVP
inside the power supply has decreased.
Reserved bit
6, 7
reserved
(Alarm is not allocated)
Indicates that the power supply
8
CNT OFF
is remote off
Indicates that an error occurred
9-13
SYST EM
inside the power supply.
Alarm is not allocated because
14, 15
reserved
it is a reserved bit.
Please contact us when the SYST EM error occurs.