Operation

Life Expectancy
Control Signal
Adjustment
Page 8
A continuous 0 to 10 Vdc signal from a controller to wire Y operates the damper
actuator. The angle of rotation is proportional to the control signal. A 0 to 10 Vdc
position feedback output signal is available between wires U and G0 (system neutral) to
monitor the position of the damper motor.
In the event of a power failure, depending on load, the actuator may not hold the
commanded (or new) position. In the event only the control signal is lost, the actuator
returns to the "0" position.
In the event of a blockage in the damper, the actuator is overload protected over the full
range to prevent damage to the actuator.
An improperly tuned loop will cause excessive repositioning that will shorten the life of
the actuator.
GBB/GIB 163x GBB/GIB 164x
The offset (start point) and span of the control signal can be adjusted. The offset point,
U0, (start point) can be adjusted between 0 to 5 Vdc. The span, ∆U, can be adjusted
between 2 to 30 Vdc.
Ys
Mechanical positioning range
(100% = angle of rotation 90°)
Yu
Control signal
U0
Offset (start point)
∆U
Span
1. Uo =0V, ∆U = 2V
2. Uo = 5V, ∆U = 30V Maximum working range
3. Uo = 0V, ∆U ≈ 10V Factory setting
Figure 15. Minimum, Factory Setting, and
GBB/GIB Series Non-spring Return, 24 Vac, Modulating Control
Minimum working range
for Ys = 100%
for Ys = 100%
Maximum Control Signal Adjustment.