6. Installation and commissioning
6.1 Mounting
Manual motor starters can be mounted as follows:
−
Fixed on a 35 mm top hat rail according to DIN EN 60715 (35 x 15 or 35 x 7.5 mm).
−
Mounted using a screw fixing on a wall/panel. Manual motor starters can be fastened to the wall/panel using
screws. MS116/MS132 manual motor starters require an additional accessory.
Mounting:
6.1.1 Mounting position and minimum distances
When mounting the manual motor starters, keep the following clearances to grounded or live parts and insulated
conduit ducts according to IEC 60947-2:
−
Single installation:
left and to the right.
−
Group installation:
than 9 mm.
6.1.1.1 Mounting position
Mounting positions 1 until 6 are permitted for manual motor starters.
Pos. 4
APR I L 19
MA N UA L MOTOR START ER G UI D E
Figure 29: Mounting of a manual motor starter.
there must be no directly attached contactor and there is a minimum gap of 9 mm to the
the contactor must be mounted directly or the gap to the left or the right must be less
Pos. 2
Pos. 3
Pos. 1
Pos. 1 ± 30°
Figure 30: Mounting position of a manual motor starter.
Dismantling:
Pos. 5
Pos. 6
48/ 80