Frequencies And Direct Current (Dc) - ABB MS116 Manual

Manual motor starter
Hide thumbs Also See for MS116:
Table of Contents

Advertisement

4.3 Frequencies and direct current (DC)

The magnetic trip values for manual motor starters are valid for frequencies from 50 to 60 Hz. Frequencies other
than 50/60 Hz will have an impact on the instantaneous short-circuit release. In the range from 45 to 66 Hz, the oper-
ating values of the instantaneous short-circuit release are within tolerance. For frequencies above 60 Hz, or for direct
current (DC), the operating value of the instantaneous short-circuit release is increased; for frequencies below 50 Hz,
the operating value of this magnetic release is decreased. Correction factors for these applications are shown below.
2
1,8
1,6
DC Value for MS132
1,4
DC Value for MS165
1,2
1
0,8
50
Thermal tripping characteristics for manual motor starters are valid for DC and AC with frequencies from 16.66 Hz to
400 Hz. For three-pole loads and currents of between 3 - 13 times the set current, the tolerance of the tripping time is
±20 %.
In contrast to alternating current (AC), no current passes take place with direct current (DC). Since current-limiting
circuit-breakers do not rely on a current zero crossing to extinguish the arc like contactors, they have hardly any re-
duced switching capacity in the case of DC short-circuits compared to alternating current.
In the case of a DC short circuit, the current increase in the first phase is quite comparable to that in the case of al-
ternating current (depending on the time constant of the DC circuit). Only the current increase (the steepness of the
short-circuit current) is crucial for the opening of the contacts in current-limiting circuit-breakers. As soon as the arc
is actively conducted from the blowing field into the quenching chamber and extinguished there, the short circuit is
switched off, regardless of when and if a current zero crossing follows.
For symmetrical heating of the thermal overload releases it is also mandatory for circuit-breakers to connect all poles
in series (mandatory for differential tripping, analogue thermal overcurrent motor protection relays). The series con-
nection also leads to a faster shutdown.
APR I L 19
MA N UA L MOTOR START ER G UI D E
100
150
200
Frequency in Hz
Figure 25: Diagram of different frequencies and direct current (DC).
250
300
350
MS132
MS165
400
45 /80

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms132Ms132-ktMo132Mo165Ms165Ms132-k ... Show all

Table of Contents