6.1.1.2 Minimum distance
The following table shows the minimum distance to other units of the same types and also to an electrically conduc-
tive wall (earthed).
Minimum distance to other
units of the same type [mm]
Minimum distance to elec-
trically conductive wall
(earthed) [mm]

6.2 Connection

The manual motor starter can be supplied either from the bottom or from the top (for non-UL applications).

6.2.1 Connection Types

The manual motor starter is available with the following types of connection:
Screw terminals
Push-in Spring terminals
Push-in Spring terminals allow conductors to be easily connected directly. The special contact spring allows easy insertion and
guarantees a good contact quality.

6.2.2 Connection cross sections

6.2.2.1 Connection cross sections for screw connection technology
The following tables show the permissible conductor cross-sections for the main connections and auxiliary conduc-
tor connections for sizes MS116, MS132, MO132, MS165 und MO165.
For MS116:
M3.5
MS116 ≤ 16 A
0.8 ... 1.2 Nm / 10 ... 12 Ib.in
M4
MS116 ≥ 16 A
2 Nm / 18 Ib.in
For MS132 and MO132:
MS132 ≤ 10 A
M3.5
MO132 ≤ 10 A
0.8 ... 1.2 Nm / 10 ... 12 Ib.in
MS132 ≥ 16 A
M4
MO132 ≥ 16 A
2 Nm / 18 Ib.in
For MS165 am MO165:
MS165
M6
MO165
4 Nm / 10 ... 12 Ib.in
Table 15: Connection cross sections for screw connection technology for manual motor starters.
APR I L 19
MA N UA L MOTOR START ER G UI D E
Horizontal
Vertical
Horizontal - up to 400 V AC
Horizontal - up to 690 V AC
Vertical
Table 14: Minimum distance by mounting.
ø 5.5 mm
1/2 x 1 ... 4 mm
Pozidriv
No. 2
ø 6.5 mm
1/2 x (1...2.5) (2.5...6) mm
ø 5.5 mm
1/2 x 1 ... 4 mm
Pozidriv
No. 2
ø 6.5 mm
1/2 x (1...2.5) (2.5...6) mm
Pozidriv
1/2 x 1 ... 50 mm
ø 6.5 mm
No. 2
1/2 x AWG 16...0
MS116
MS132
0
150
150
0
>1.5
>1.5
75
2
1/2 x 0.75 ... 2.5 mm
2
1/2 x AWG 16 ...12
2
1/2 x (1...2.5) (2.5...6) mm
2
1/2 x AWG 16...8
1/2 x 0.75 ... 2.5 mm
2
2
1/2 x AWG 16 ...12
1/2 x (1...2.5) (2.5...6) mm
2
2
1/2 x AWG 16...8
2
1/2 x 1 ... 35 mm
2
1/2 x AWG 16...0
MS165
0
0
150
0
0
>1.5
75
75
1/2 x 0.75...2.5 mm
2
9 mm
1/2 x 0.75...6 mm
2
10 mm
1/2 x 0.75...2.5 mm
2
9 mm
1/2 x 0.75...6 mm
2
10 mm
2
1/2 x 1...35 mm
16 mm
49/8 0