ABB MS116 Manual page 25

Manual motor starter
Hide thumbs Also See for MS116:
Table of Contents

Advertisement

2.4.6.1
Building rules for
The maximum capacity for MS116, MO132 and MS165
One front mounting auxiliary contact HKF1,
Two accessories mounted on the right:
one SK1 signal contact alarm and one HK1auxiliary contact
or two HK1 auxiliary contacts
One AA1 shunt trip or one UA1 undervoltage release on the left side
The maximum capacity for MS132 or MS165
One front mounting auxiliary HKF1 contact,
Two accessories mounting on the right:
one SK1 signal contact alarm and one auxiliary HK1contact
or two auxiliary HK1 contacts
or one
or one CK1
One AA1 shunt trip or one undervoltage UA1 release on the left side (note: The combination of MS132-K +
UA1 + CK1 is not possible)
APR I L 19
MA N UA L MOTOR START ER G UI D E
manual motor starters with accessories
Figure 6: The maximum capacity for MS116, MO132 and MS165
Figure 7: The maximum capacity for MS132 or MS165
short-circuit
CK1
indicator
short-circuit indicator
and one SK1
signal contact alarm
and one auxiliary HK1contact
2 5/8 0