Status - Siemens 6DR55 Series Manual

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

Functions/operation via PROFIBUS PA
Hex
Dez
Accompanying
status code
1F
31
READBACK, POS_D
47
71
READBACK, POS_D
48
75
READBACK, POS_D
4F
75
READBACK, POS_D
53
83
READBACK, POS_D
80
128
SETPOINT (SP),
READBACK,
POS_D
84
132
READBACK, POS_D
8D
141
READBACK,
8E
142
READBACK, POS_D
A3
163
SETPOINT (SP)
A4
164
READBACK, POS_D
Table 9
Status codes
5.3.2.2
Diagnostics
148
PDM display
Cause
bad,
Function block has been
out of service,
disabled by command. Device
value
will move to safety position
constant
uncertain,
Connection is disconnected or
last useful
the SETPOINT status is not
value, value
"Good". Positioner will move
constant
to safety position, the para--
meterized safety setting is set
to "retain last valid value"
uncertain,
Connection is disconnected or
substituted
the SETPOINT status is not
value, value
"Good". Positioner will move
constant
to safety position, the parame-
terized safety setting is set to
"issue default value"
uncertain,
After powering up an initial
iinitial value,
value is entered ion the device
value
memory
constant
uncertain,
Device will be controlled
value
locally
uncertain
Good
Normal operation
Good, update
A parameter relevant to the
event
device has been changed.
This display will expire after
10 sec.
Good, alarm
Out of tolerance below lower
value fallen
parameterized alarm limit.
below
Alarm output A1 or A2 will be
activated
Good, alarm
Out of tolerance above upper
value
parameterized alarm
exceeded
limit.Alarm output A1 or A2 will
be activated
Good,
Command to take up the
Go to
safety position
Fail--Safe
Good,
The travel integral limit value
maintenance
has been exceeded by the ab-
requested
solute travel integral
As well as status information the device can also report active
information regarding the device condition. Diagnostics are important
information which can be used in an automation system purposes of
determining remedial action.
Action
For normal operation reinstate
target mode "AUTO"
Check the connection and
make sure that the
SETPOINT (SP) is
accompanied by a status of
80 hex., 128 decimal (Good)
Check the connection and
make sure that the
SETPOINT (SP) is
accompanied by a status of
80 hex., 128 decimal (Good)
Discard the value in the
application program
------
------
------
For normal operation the
status 80 hex., 128 decimal
(Good) must be restored
Perform maintenance and
reset the reports using
SIMATIC PDM
SIPART PS2 PA Manual
A5E00127926--05