Service And Maintenance - Siemens 6DR55 Series Manual

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

Service and maintenance

SIPART PS2 PA Manual
A5E00127926--05
The positioner is largely maintenance--free. The positioners are fitted
with filters in the pneumatic connections as protection against coarse
particles of dirt. This dirt will be deposited under pressure on to the filter
and the filters may clog and impair the function of the positioner. In this
case the filters can be cleaned as follows.
Positioner in metal housing and explosion--proof version
1. Switch off the pneumatic power supply and remove the pipes.
2. Remove the metal filters carefully from the holes and clean (e.g.
with compressed air).
3. Insert the filters.
4. Re--connect the pipes and supply pneumatic energy.
Positioner in plastic housing
Removal
1. Switch off the pneumatic power supply and remove the pipes.
2. Unscrew the cover
3. Remove the three screws from the pneumatic connector strip.
4. Remove the filters and O--rings behind the connector strip.
5. Clean the filters (e.g. with compressed air).
Installation
6. First insert the filters in the recesses in the plastic housing and then
place the O--rings on the filters.
7. Align the pneumatic connector strip on the two lugs and screw tight
with the three self--tapping screws.
Service and maintenance
6
159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sipart ps2 pa

Table of Contents