MasterShunt 500 – User and Installation manual
Adding the MasterShunt 500 to a CZone network
1 Disconnect the backbone at the closest backbone connection and add in a tee connector.
2 Reconnect the backbone connection(s) with the new tee connector in place.
If you want to add the MasterShunt 500 at the end of the backbone, remove the terminator, add the new tee
connector and attach the terminator to the side of the connector.
3 Connect the RJ45 CZone/MB drop cable to the black coupler on the tee and then connect to the MasterShunt
500.
Adding the MasterShunt 500 to a MasterBus network
1 Disconnect a MasterBus cable or Terminator from the closest MasterBus device and connect it to the
MasterShunt 500.
2 Connect the new MasterBus cable to the other MasterBus device and then connect to the MasterShunt 500.
3 Ensure that the network is properly terminated.
See section 4.2 for more information on system integration.
Step 7. Check all wiring. If all wiring is OK: (re)connect the positive battery cable.
Step 8. Proceed with chapter 5, SETTINGS.
4.4

Placing a fuse inside

By default the MasterShunt 500 is equipped with a busbar inside. If the MasterShunt 500 is installed close to the battery, this
busbar may be replaced by either an ANL type or Class T main fuse (500A), saving both space and cost. Another option is to
place a fuse elsewhere in the system.
Note: Always have the selected fuse checked by qualified personnel to prevent any unnecessary fuse melts when going fully
operational.
Execute the following procedure to replace the busbar by a fuse:
Step 1. Disconnect the electrical power:
Step 2. Remove the two transparent covers.
Step 3. Unlock and remove upper casing.