Trouble Shooting - Mastervolt MasterShunt 500 User And Installation Manual

Enhanced battery monitor
Hide thumbs Also See for MasterShunt 500:
Table of Contents

Advertisement

20
MasterShunt 500 – User and Installation manual

7 Trouble shooting

Please contact your local Mastervolt Service Centre if you cannot correct a problem with the aid of the malfunction table below.
See www.mastervolt.com for an extended list of Mastervolt Service Centres.
Failure
Display shows no
MasterShunt 500
No voltage on load
side of MasterShunt
500
No accurate time
remaining function
State of Charge not
accurate
Battery is fully charged
but SOC function does
not show "100%"
State of Charge does
not return to 100%
after a long period of
charging
Wrong language is
displayed
Alarm function is
triggered by a short
time voltage dip
The communication
LEDs blink alternately,
indicating an alarm
situation.
Possible cause
No terminating device placed at the
ends of the MasterBus network
Network is configured as a ring
network
T-connections in the network
Error in the wiring
Display not set up to show all devices
MasterShunt 500 is not configured in
CZone configuration file
MasterShunt 500 Dipswitch not
correct
Fuse blown
Wrong setting of the nominal battery
capacity
Part of the load or the charger is
connected at the battery side of the
MasterShunt 500
Wrong setting of the nominal battery
capacity
Self-discharge of the batteries which
was not recorded by the MasterShunt
500
Charging system has not met the
conditions for a fully charged battery
Wrong setting of the float voltage
Wrong setting of the language at the
MasterShunt 500
Wrong setting of the language at
displaying device
Wrong setting of the parameters
Wrong setting of the alarm delay time.
All failures can result in an alarm
situation.
What to do
A MasterBus networks needs a terminating device on both
ends of the network. Check if available (see Section 4.2).
Ring networks are not allowed. Check the connections of
the network (see section 4.2).
Check if T-connections are made in the network. T-
connections are not allowed (see section 4.2).
Check the cables and terminating devices (see section
4.2).
Check manual of the display.
Open CZone Configuration Tool and check.
Open CZone Configuration Tool and check with Force
Dipswitch for Address.
Investigate the cause of the blown fuse. Then replace the
fuse (see section 6.2).
Correct the battery capacity setting (see section 5.1.1,
Battery).
Check whether all load and charger connections are at the
load side of the MasterShunt 500 (see section 4.2).
Correct the battery capacity setting (see section 5.1.1,
Battery).
Recharge the batteries for at least 24 hours.
See section 3.1 for an overview of the conditions for a fully
charged battery.
Lower the setting of the float voltage of the MasterShunt
500 by 0.1V (see section 5.1.1, Battery).
Adjust the language setting (see section 5.1.1, General).
Each separate connected device can have its own
language setting. See the user manual of the connected
remote control.
Set the parameters correctly (see section 5.1.1, Alarm
levels).
Increase the delay time (see section 5.1.1, Alarm levels).
Look at your remote control to find out which failure needs
to be corrected.