4.16 Set Up Process Variable Input Page (COMMANDER 301 only)
Information.
•
This information is only for the COMMANDER 301 when the custom linearizer function
is used. For normal input setting up, refer to Section 4.5.
•
Up to 20 breakpoint custom linearizer.
•
Cold junction compensation for thermocouple inputs.
SEtUP
PrCESS
IntYPI
U.Lt
MAMP
VOLt
ohM
tCLP
rtd
LNtYPI
CUSt
5 2
3 2
SQrt.
MVLt
L–UNtI
MAMP
dEG C
VOLt
ohM
Page Header –
Set Up Process Variable Input
Process Variable Input Type
Select the input type required:
–
MU. L t
MAMP
–
–
V. O Lt
–
ohM
tCPL
–
–
rtd
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Linearizer Type
Select the custom linearizer:
–
Custom linearizer
CUSt
Linearizer Units
If thermocouple or RTD was selected for
, select the temperature units required, °C or °F.
Input Type
Continued on next page.
4 CONFIGURATION...
Millivolt (≤2000 mV)
Current
Voltage
Resistance
Thermocouple*
Resistance thermometer
.
Process Variable