...4.2 Set Points Page
rSP–LO
0
r–AdJ
no
dUAL
NONE
rAtIO
1.000
b–AdJ
no
bIAS
0
Remote Set Point Low Limit
This is the minimum value to which the remote set point
can be adjusted.
Select the value required. The decimal point position is set
automatically.
Remote Set Point Ratio Adjust Enable
This frame enables or disables the display and adjustment
of the remote set point ratio in the Operating Page (see
Section 5.2 of the Operating Guide
Select
to enable or
YES
Remote Set Point Ratio
This is a scaling factor, i.e. multiplies the remote set point
input by the ratio value set. Set the required remote set
point ratio, between 0.010 and 9.999 in 0.001 increments.
Remote Set Point Bias Adjust Enable
This frame enables or disables the display and adjustment
of the remote set point bias in the Operating Page (see
Section 5.2 of the Operating Guide
Select
to enable or
YES
Remote Set Point Bias
This is an offset value set as a proportion of display span
(may be ± the span value).
Set the remote set point bias in engineering units.
Continued on next Page.
4 CONFIGURATION...
.
)
to disable.
no
.
)
to disable.
no