ABB COMMANDER 300 Programming Manual page 32

Universal process controllers
Hide thumbs Also See for COMMANDER 300:
Table of Contents

Advertisement

...4 CONFIGURATION
...4.10 Set Up Control Page
Ht-COOL
OPtYPE
SINGLE
t–PrOP
P–PrOP
C–PrOP
bNdLSS
PF M OdE
LASt
MANUAL
AUtO
LASt
or
MANUAL
Aut OP
0.0
Power
AUtO
Failure
Mode
MAN OP
LASt
Power
Failure
Mode
LASt
AMA OP
AUtO
30
Second Output Type
Select
for analog output.
Power Failure Mode
Select the default power failure mode required following a
power interruption or failure:
Power
Failure
Mode
Auto to Manual Power Fail Output
A control output value can be set when the power down
state is
Set the control output value required following a power
failure, between 0.0 and 100.0% in increments of 0.1%.
is
AUtO
Manual to Manual Power Fail Output
This is the control output value required when power down
state is
Set the control output value required following a power
failure, between 0.0 and 100.0% in increments of 0.1%, or
LASt
MANUAL
Auto Power Fail Output
This is the output value required when the power down
state is
Set the output value required following a power failure,
between 0.0 and 100.0% in increments of 0.1 %, or
If
AUtO
up. If boundless control type is selected, this parameter
must be set to
Continued on next page.
for time proportioning output or
t–PrOP
restart in the same mode existing prior
LASt
to power failure.
restart in Manual mode. (Not applicable
MANUAL
when
selected).
restart in Auto mode.
AUtO
and the power failure mode is
AUtO
Note. This setting has no effect if power failure mode
.
and power failure mode is
MANUAL
.
the
LASt
present prior to the power failure is
retained.
and the power failure mode is
AUtO
is selected normal start-up is restored on power
.
AUtO
boundless
control
MANUA
percentage
control
C–PrOP
type
is
.
MANUAL
L.
output
.
AUtO
.
AUtO