...4 CONFIGURATION

4.8 Set Up Display Page

Information.
Set up engineering ranges and units.
Programmable increments on deviation bargraph.
Adjust display brightness.
dISPLY
PAGE
dIS–HI
1000
dEC–Pt
1000
dIS–LO
0
INCMNt
1
UNItS
dEG C
brIGHt
7
SEtUP
CONtrL
24
Page header – Display Page.
Display Full Scale
Set the display value which represents the maximum
process variable input signal, between –9999 and +9999.
Example
pressure range of 50 to 250 bar, set 2500. The decimal
point position is set at the next parameter.
Decimal Point Position
Set the required number of decimal places for both the
display full scale and display zero values. In the example
shown above, set the decimal point position to show
increments of 0.1 bar, i.e. 250.0.
Display Zero
Set the display value which represents the minimum
process variable input signal, between –9999 and +9999.
In the example shown above, set 50.0. The decimal point
position is set automatically.
Percentage Increment Per Bar (Bargraph)
This frame sets the percentage deviation from set point
that each bar of the
Fig. 4.1 in the Operating Guide
Set the value required, between 1 and 10% of display
span.
Display Units
Select the required display units,
to represent the process variable.
Brightness Adjustment
Select the required display brightness between 4 and 10.
Return to top of
programming page.
C–PrOP
o r
OUtPUt
– For an input range of 4 to 20mA representing a
Deviation Bargraph
Display Page
represents – see
.
,
, or
dEG C
dEG F
or advance to the next
NONE