4 PROFINET IO Diagnosis
4.1 Diagnosis HTML Page of EN100
The PROFINET IO diagnosis page contains the following information blocks:
IO device
IO modules
Telegram receive/transmit statistics
LLDP neighborhood information
Event list
IO Device
Diagnosis
Status
Station name
Function
Location
Installation date
Description
MAC addresses
FO power budget
IO Modules
NOTE
The IO modules table only contains entries if the SIPROTEC IO device communicates with the IO controller.
IO modules in the SIPROTEC device are plugged dynamically as specified by the parameterization in the IO
controller when the communication is initialized.
If no PROFINET IO communication exists, no IO modules are plugged.
The following table shows the IO modules parameterized in the IO controller for the SIPROTEC device and the
status of these IO modules in the SIPROTEC IO device.
Diagnosis
Slot
Module name
Module ID
Subslot
IO direction
88
Communication status with IO controller (online or offline)
Station name of the SIPROTEC device
Identification and Maintenance data I&M1 through I&M3 stored in the device and
written via acyclic PROFINET IO telegrams (see Chapter 4.3)
X1: Interface MAC address
P1, P2: Port MAC addresses
Fiber optical power budget of the receive signal on the ports P1 and P2 in dB
Slot number (18 IO modules max. plus DAP can be plugged)
Name of the plugged IO module
Identification number of the module type as per GSD file
Subslot number
Data direction (input data or output data)
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
Description
Description
C53000-L1840-C360-1, Edition 08.2012