Data Type Double-Point Indication (Dp, Input)/Double Command (Dc, Output) - Siemens SIPROTEC PROFINET IO Manual

Communication module
Table of Contents

Advertisement

2.3.3

Data Type Double-Point Indication (DP, Input)/Double Command (DC, Output)

Number of byte values:
Range of values:
0 = "not applicable"/
disturbed state for DP and
idle state for DC
1 = OFF
2 = ON
3 = disturbed state for DP,
not allowed for DC
NOTE
Depending on the data type selected in DIGSI, the values 0 and 3 for double-point indications have the
following meaning:
Type DP:
Type DP_I:
"not applicable":
...
Figure 2-7
NOTE
The data type double command requires the associated command feedback to be parameterized as double-
point indication.
A double command with a single-point indication as feedback or without feedback acquisition is controlled in
the same way as a single command via PROFINET IO. This means that the processing of a double command
via PROFINET IO depends on the type of the associated feedback.
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
1/4 (2 bits)
bit 1 = 0 and bit 0 = 0
bit 1 = 0 and bit 0 = 1
bit 1 = 1 and bit 0 = 0
bit 1 = 1 and bit 0 = 1
0 = "not applicable", 3 = disturbed state "00" or disturbed state "11"
0 = "not applicable" or disturbed state "00", 3 = disturbed state "11"
the indication is not routed (not connected to a binary input)
7
4
3
2
to 2
2
...
Bit 1
DP/DC 2
4 double-point indications/double commands max. per byte
Data Type: Double-Point Indication/Double Command
2.3 Data-Type Definitions for IO Data Exchange
1
2
2
2
Bit 0
Bit 1
Bit 0
DP/DC 1
2 PROFINET IO in SIPROTEC
0
2
...
23