Siemens SIPROTEC PROFINET IO Manual page 66

Communication module
Table of Contents

Advertisement

3 Parameterization
3.2 Parameterization with DIGSI
Move the mouse pointer in the source and destination columns over port B (or port F) and find out which
column is assigned to PROFINET IO (highlighted in red in Figure 3-14).
When you hover briefly over the letter B, the protocol used is displayed (yellow text).
If necessary, adjust the preset routing in the Configuration Matrix in your SIPROTEC device/system as
follows. If you do not wish to make any modifications in the DIGSI Configuration Matrix, continue with the
Time Synchronization section in this chapter.
To delete all preset routings in order to reconfigure them, right-click port B or system interface S in source
or destination, respectively. Subsequently, click the prompt Delete routings on Port B (PNIO-EN100)
or Delete routings on system interface.
A window is displayed which informs you that this is not possible or which confirms how many entries are
deleted or not deleted. Click OK to confirm the information:
Figure 3-15
You can conclude from the source system interface and destination system interface columns in the DIGSI
Configuration Matrix whether an information item is routed to the system interface (PROFINET IO).
A cross ('X') in this column marks the associated information item as "routed to the system interface".
Source System Interface
Routing to the source system interface is possible for the following information types:
IntSP
IntDP
C_XX
CF_XX
66
Information on the Deletion Process
Internal single-point indications (markers)
Internal double-point indications (markers)
Commands without feedback acquisition
Commands with feedback acquisition
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012